SECTION 4: APPLICATION
CONSIDERATIONS
4-1
ZONE INTERLOCKING CAPABILITIES
To minimize damage to the system, faults should be
cleared as quickly as possible. Zone selective interlock-
ing provides this capability better than a system with only
selective coordination.
When the “Ground Zone Interlocking” feature is utilized,
an immediate trip is initiated when the fault is in the
breaker’s zone of protection, regardless of its preset time
delay. When the “Phase Zone Interlocking” feature is uti-
lized, the inverse time overcurrent and short delay phase
elements work as follows. The short delay phase element
will initiate an immediate trip when the fault is in the
breaker’s zone of protection, regardless of its preset time
delay. For the inverse time overcurrent phase ele-
ment, the current sensed by the Digitrip 3000 must
exceed 300 percent (3 x I
n
) for the zone selective
interlocking to initiate an immediate trip signal. This
interlocking signal requires only a pair of wires from the
downstream breaker to the upstream breaker.
When a Digitrip 3000 initiates a trip signal, the zone inter-
locking signal stays active for an additional 175 millisec-
onds. Therefore, if a downstream Digitrip 3000 is zone
interlocked to an upstream Digitrip 3000, the downstream
breaker will have 175 milliseconds to clear the fault
before the upstream Digitrip 3000 is allowed to react to
that same fault.
Zone interlocking, therefore, provides fast tripping in the
zone of protection, but gives positive coordination
between mains, feeders and downstream breakers. For
faults outside the zone of protection, the Digitrip 3000 on
the breaker nearest the fault sends an interlocking signal
to the Digitrip 3000 protective devices of the upstream
breakers. This interlocking signal restrains tripping of the
upstream breakers until their set coordination times are
reached. Thus zone interlocking, applied correctly, can
result in minimum damage with a resultant minimum dis-
ruption of service.
Zone selective interlocking is available on Digitrip 3000
Protective Relays for the inverse time and short time
functions on the phase and ground elements. Refer to
Figure 4-1 for a typical phase zone selection interlocking
wiring diagram or refer to Figure 4-2 for a typical ground
zone selection interlocking wiring diagram.
Содержание Cutler-Hammer Digitrip 3000
Страница 18: ...I B 17555C Effective November 1999 Page 12 Fig 2 1 Typical Communications Wiring Diagram...
Страница 27: ...I B 17555C Effective November 1999 Page 21 Fig 3 1 Digitrip 3000 Typical Wiring Diagram...
Страница 36: ...I B 17555C Effective November 1999 Page 30 Fig 3 11 Local Programming Sequence Flow Chart...
Страница 37: ...I B 17555C Effective November 1999 Page 31...
Страница 48: ...I B 17555C Effective November 1999 Page 42 Fig 7 1 Inverse Time Overcurrent Phase I4T Curves SC 5390 92B...
Страница 49: ...I B 17555C Effective November 1999 Page 43 Fig 7 2 Inverse Time Overcurrent Phase I2T Curves SC 5391 92B...
Страница 50: ...I B 17555C Effective November 1999 Page 44 Fig 7 3 Inverse Time Overcurrent Phase IT Curves SC 5392 92B...
Страница 51: ...I B 17555C Effective November 1999 Page 45 Fig 7 4 Inverse Time Overcurrent Phase Flat Curves SC 5393 92B...
Страница 52: ...I B 17555C Effective November 1999 Page 46 Fig 7 5 Short Delay Phase Curves SC 5394 92B...
Страница 53: ...I B 17555C Effective November 1999 Page 47 Fig 7 6 Inverse Time Overcurrent Short Delay Curves SC 5395 92B...
Страница 54: ...I B 17555C Effective November 1999 Page 48 Fig 7 7 Instantaneous Curves SC 5396 92B...
Страница 55: ...I B 17555C Effective November 1999 Page 49 Fig 7 8 Inverse Time Overcurrent Ground I4T Curves SC 5399 92B...
Страница 56: ...I B 17555C Effective November 1999 Page 50 Fig 7 9 Inverse Time Overcurrent Ground I2T Curves SC 5400 92B...
Страница 57: ...I B 17555C Effective November 1999 Page 51 Fig 7 10 Inverse Time Overcurrent Ground IT Curves SC 5401 92B...
Страница 58: ...I B 17555C Effective November 1999 Page 52 Fig 7 11 Inverse Time Overcurrent Ground Flat Curves SC 5402 92B...
Страница 59: ...I B 17555C Effective November 1999 Page 53 Fig 7 12 Short Delay Ground Curves SC 5403 92B...
Страница 60: ...I B 17555C Effective November 1999 Page 54 Fig 7 13 ANSI Moderately Inverse Curves SC 6685 96...
Страница 61: ...I B 17555C Effective November 1999 Page 55 Fig 7 14 ANSI Very Inverse Curves SC 6686 96...
Страница 62: ...I B 17555C Effective November 1999 Page 56 Fig 7 15 ANSI Extremely Inverse Curves SC 6687 96...
Страница 63: ...I B 17555C Effective November 1999 Page 57 Fig 7 16 IEC A Moderately Inverse Curves SC 6688 96...
Страница 64: ...I B 17555C Effective November 1999 Page 58 Fig 7 17 IEC B Very Inverse Curves SC 6689 96...
Страница 65: ...I B 17555C Effective November 1999 Page 59 Fig 7 18 IEC C Extremely Inverse Curves SC 6690 96...
Страница 66: ...I B 17555C Effective November 1999 Page 60 Fig 7 19 IEC D Flat Curves SC 6691 96...
Страница 68: ...I B 17555C Effective November 1999 Page 62...
Страница 73: ...I B 17555C Effective November 1999 Page A5 Fig A 7 DT3001 Typical Wiring Diagram...
Страница 76: ...I B 17555C Effective November 1999 Page A8...
Страница 81: ...I B 17555C Effective November 1999 Page B5 Fig B 2 Digitrip 3010 3020 Dimensions Inches...
Страница 83: ...I B 17555C Effective November 1999 Page B7 Fig B 3 Digitrip 3010 3020 Typical Wiring Diagram...
Страница 89: ...I B 17555C Effective November 1999 Page B13...
Страница 90: ...I B 17555C Effective November 1999 Page B14...
Страница 91: ...I B 17555C Effective November 1999 Page B15...