I.B. ATS-V003
Page 27
Effective 6/98
Step 3: Verify that the voltage selection plug is in the
proper position to match the system voltage.
Step 4: Look for any obviously overheated components.
Determine the cause and rectify, if possible.
Replace defective components after the cause
is determined.
Step 5: Manually ratchet the mechanism to the NOR-
MAL position. Verify whether or not the system
voltage now appears on the load terminals.
If YES:
Proceed to check logic for problems
in respective logic instruction book.
If NO:
Check all power connections and
the switching mechanism.