manualshive.com logo in svg
background image

Power Supply Notes

All low-current ground-fault sensors are sensitive devices that 

require reasonable care in system design to avoid false trips caused 

by high electrical noise levels. Keep in mind that the best way to 

reduce noise in a system is to suppress it at its source.

• 

Keep the sensor power isolated from noisy circuits.

• 

Do not power the sensor with the same circuit that switches con-

tactors or other high current inductive loads.

System Grounding

Good design practice and code require that all AC power systems 

be grounded. The EGF Series sensors are designed to work on 

grounded AC power systems. They may not operate properly on 

ungrounded systems.

Specifications

Specification

Value

Power Supply

120 VAC (Operates from 66-132 V) 

24 VAC/DC (Operates from 19.2-28.8 V)

Voltage Range

Up to 1,500 VAC (Monitored Circuit)

Power Consumption

2.5 W

Output

Latching Electromechanical Relay 

Normally Open Models Latch Closed Upon Sensed Fault 

Current 

Normally Closed Models Latch Open Upon Sensed Fault 

Current

Output Rating

1.0 A @ 120 VAC 

2.0 A @ 30 VAC

Response Time

At 5% Over Setpoint: 200 ms 

At 50% Over Setpoint: 60 ms

At 500% Over Setpoint: 15 ms

Setpoint Range

Selectable by Model 

   Fixed Setpoints: 50, 100 mA 

   Adjustable Setpoints: 5, 10, 30 mA (By Jumper)

Setpoint Adjustment

See “Adjust Setpoint” in “Operation” Section

Frequency Range

50-400 Hz (Monitored Circuit)

Housing

UL94 V0 Flammability Rated

Dimensions

Case: 2.5 in. H x 2.8 in. W x 1.5 in. D (64 x 71 x 38 mm)

Aperture: 0.75 in. (19 mm)

LED

Green = Power Supply Energized 

Red = Relay Has Operated

Environmental

Operating Temperature: +5 to +158°F (-15 to +70°C)

Humidity: 0-95% RH, Non-Condensing

Approvals

UL Recognized, E313337

CE

RoHs Compliant

Ttsoing

To test operation, gently press the TEST button. This simulates a fault 

and tests the internal switching circuits. After the test is complete, 

reset the sensor with a momentary dry contact on Terminals 5 and 

6. CAUTION: Any circuit connected to the sensor will be operated.

Adjusoing StopNino

While not as precise as having it set at the factory, the setpoint can be 

adjusted in the field. See wiring diagram for location of potentiometer. 

The best way to adjust the trip point is to develop a load of the mag-

nitude at which you want the sensor to trip. A resistor of 4,000 Ohms 

should provide a load of 30 mA at 120 VAC, or a night light bulb of 4 

watts should relate to 33 mA. With the load energized and passing 

through the sensing aperture, turn the potentiometer clockwise until the 

sensor trips. Then, back one-eighth of a turn and the setpoint should be 

correct. 
When used with an external current transformer (CT), the sensor will 

be set to trip at a point much lower than without the CT.  This set point 

adjustment should be done with the load passing through the CT in that 

application.

3

EATON 

www.eaton.com

 

Instructions Publication 

P51923

Effective July 2017

CurrentWatch™ EGF Series Ground Fault Sensors 

120 VAC or 24 VAC/DC, N.O. or N.C. SPST 

Latching Relay Output

Отзывы: