manualshive.com logo in svg
background image

Introduction

The CurrentWatch™ EGF Series is a family of  

ground fault (earth leakage) sensors. Ground  

fault sensors help protect people, products, and  

processes from damage by ground fault  

conditions by monitoring all current-carrying  

conductors in grounded single- and three- 

phase delta or wye systems. 
The EGF Series with mechanical outputs are  

available in solid-core housings with a choice of N.O. or N.C. SPST 

latching relays. All mechanical models can be ordered with a fixed 

setpoint or with a “tri-set” option, which provides three factory-set, 

field adjustable setpoints.

Note:

N

This manual only covers EGF Series models listed in the above table. 

This installation manual does not cover EGF Series models with auto-reset.  

Quick Install Guide

The below steps can be followed to quickly install a CurrentWatch 

EGF Series switch.
1.  Run all current carrying conductors through sensor window, 

using an auxiliary current transformer if conductors do not fit.

2.  Mount the sensor to a surface if needed.
3.  Connect output and power wiring:

a.  Use up to 14 AWG copper wires,
b.  Ensure power and load matches those shown on the sensor 

label.

4.  Test the unit:

a.  Pressing the “TEST” button will test the sensor’s internal 

circuits,

b.  CAUTION: The output and any c

onnected loads will switch 

during the test process.

Installation and Mounting 

Considerations for all EGF Series sensors…

• 

Run wire to be monitored through the aperture (opening) in the 

switch body, making sure all wires are oriented so that current 

flows in the same direction (see “Principal of Operation” section 

below.

• 

These sensors can be located in the same environment as 

motors, contactors, heaters, pull-boxes and other electrical enclo-

sures.

• 

Mounting can be done in any position or hung directly on a wire 

with a wire tie.

• 

Be sure to leave at least 1.0 in. (25.4 mm) distance between sen-

sor and other magnetic devices.

Considerations for wiring EGF Series sensors…

• 

Use up to 10 AWG copper wire and tighten terminals to 4.5 in.-lbs 

/ 0.51 N·m maximum torque.

• 

Connect power wiring to terminals 1 and 2, making sure that the 

power supply matches the power rating on the sensor label.

• 

Connect output wiring to terminals 3 and 4.

Principal of Operation

Under normal conditions, the current in one wire of a two wire load 

is equal in strength but opposite in sign to the current in other wire. 

The two wires create magnetic fields that cancel, a condition known 

as “Zero Sum Current.” If any current leaks to ground (Ground Fault), 

the two currents become unbalances and there is a net resulting 

magnetic field. The EGF Series sensor detects this minute field and 

change the output state. This concept extends to three phase sys-

tems such as 3-wire Delta and to 4-wire Wye.

Single Phase 

(Phase to 

Neutral or Phase 

to Phase)

Three-Phase 

Delta 

(Includes Neutral 

if Load Uses 

Neutral)

Three-Phase 

Wye 

(Include Neutral 

if Load Uses 

Neutral)

Three-Phase 

Load  

(Using Auxiliary 

CT)

WIRING 

Use up to 14 AWG copper wire and tighten terminals to 4.5 in.-lbs / 

0.51 N·m maximum torque. See diagram below.

PNwtr

Connect power wiring to Terminals 1 and 2. Be sure that the power 

supply matches the power rating on the sensor label.

Ouopuo

Connect output wiring to Terminals 3 and 4.

Rtsto Swioch

Connect a momentary dry contact to the Reset Terminals 5 and 6. 

Limit wire run to 200 ft. (60.96 m) of 18 AWG or larger wire.

MNmtnoary Rtsto

Only close the reset terminals momentarily—the sensor will not 

work properly if the reset terminals are closed (shorted) continu-

ously. Limit wire run to 200 ft. (60.96 m) of 18 AWG or larger wire.

Paralltl Rtsto CNnntcoiNn

Multiple sensors may be connected to the same reset switch in 

parallel. Only the sensors that have detected a fault and have latched 

will be reset. A sensor will not reset unless the fault has dropped 

below setpoint.

Operation

The EGF Series latching ground fault sensors operating in one of two 

states: Reset or Latched. If control power is removed, the sensor 

remains in it’s last state (latched or reset).

Rtsto

The sensor has not detected a fault and the output is in the “nor-

mal” position. For Normally Open (N.O.) sensors, the contact is 

normally open in the reset condition. For Normally Closed (N.C.) sen-

sors, the contact is normally closed in the reset position.

Laochtd

Upon detecting a fault or when the TEST switch is pressed, the out-

put will switch and “latch.” The output will remain latched until the 

ground fault is removed and the output is reset by a momentary dry 

contact on Terminals 5 and 6.

Red Status LED (On When Tripped)

Setpoint Adjustment
(Located Under Label)

Test Button 
(Caution: Will Activate Output Relay)

External Reset Button (5 and 6)

Output (3 and 4)

Power Supply Input (1 and 2)

Power (Green) LED
(On if Power is Applied)

1

2

3

4

5

6

G

R

TEST

2

EATON 

www.eaton.com

CurrentWatch™ EGF Series Ground Fault Sensors 

120 VAC or 24 VAC/DC, N.O. or N.C. SPST 

Latching Relay Output

Instructions Publication 

P51923

Effective July 2017

Отзывы: