1. Safety Instructions

This product should be Installed and connected by skilled electri-
cians and instructed personnel in accordance with IEC/EN 60079-14 
and the respective national legislation on electrical equipment for 
explosive atmospheres. 
The national safety rules and regulations for the prevention of ac-
cidents, as well as the safety instructions, like this text set in bold-

italics in these operating instructions manual, shall be observed!
The  luminaries  must  not  be  operated  in  Zone  0  or  20  hazardous 
areas.
The requirements of IEC/EN 60079-14 regarding excessive dust de-
posits and temperature must be considered by the user. The indi-
cated  surface  temperatures  are  not  related  to  a  layer  above  5mm 
thickness.
Before opening, electrical power to the luminaire must be turn off 
during at least 10minutes!
The temperature class and explosion group stated on the luminaire 
shall be observed. To ensure adherence to the temperature class or 
surface  temperature  stated  on  the  type  label  of  the  luminaire,  the 
permissible ambient temperature shall be observed.
Light fi tting shall be used for their intended purpose and shall be 
undamaged and in a perfect and clean conditions. 
Keep tightly closed when in operation.
The technical data indicated in point 3 as well as those indicated in 
light fi tting, must be observed.
Modifi cations or design changes to this luminaries that can affect 
the explosion protection are not permitted. 
Avoid multiple, short time switching operation Only original 

EATON  Crouse-Hinds  Series 

spare  parts  may  be  used  as  replace-

ments and for repairs. 
Repairs  that  affect  the  explosion  protection  may  only  be  carried 
out by 

EATON Crouse-Hinds Division 

or by a qualifi ed electrician in 

compliance with the respective national regulations. 
Prior to being put into operation, the luminaries shall be checked in 
accordance with the instructions as per section 6.
Before initial operation, any foreign matter shall be removed from 
light fi tting, do not keep this operating instructions manual inside of 
the luminaire during its operation.

2.  Conformity with standards

This equipment is conform to the standards specifi ed in the EU-Decla-
ration of conformity. It has been designed, manufactured and tested ac-
cording  to  the  state  of  the  art  and  according  to  EN  ISO  9001  and  IEC 
80079-34.

3.  Technical data

Marking: 

 II 2 G Ex d IIC T6 Gb  

 

 II 2 G Ex de IIC T6 Gb 

 

 II 2 D Ex tb IIIC T85°C Db

EC-type examination certifi cate:  

LOM 03ATEX2036X

Rated voltage: 

220-240V, 50/60Hz

 

108-127V, 50/60Hz (on request)

Rated current (230V 50Hz): 

30mA

Power factor  

>0,95

Lamp 

PL 11W TC-SEL

Lampholder 

2G7: EN 60061-2

Luminous fl ux 

8

E

/

8

N

 at the 

end of rated operating time 

589lm/720lm

Terminals: 

2x2,5mm

2

 L and N, 6mm

2

 PE ext.,

 

use ring terminal, not included.

Degree of protection IEC/EN 60529: IP 67 
Insulation class IEC/EN 60598: 

I

Perm. ambient temperature: 

-5ºC to +40ºC

The Ta range for electronic ballast is reduced up to +40ºC 
due to their Tw, at higher temperature

 EATON Crouse-Hinds Division 

cannot gua-

rantee their normal life.

Storage temperature in original 
packaging: 

-5ºC to + 40ºC

Enclosure material  

Aluminium alloy casting (Cu free)

Glass material:  

Borosilicate glass

Enclosure surface fi nish: 

Plastic powder coating 

Color of enclosure (standard version):RAL 7032, cover RAL 7016
Dimensions: 

See Fig. 2

Cable entries: 

2x3/4”NPT or 2xM25X1,5 or  

 

 

2xM20X1,5

 

one with blanking plug.

Weight 

5,0 Kg

Batteries  

Ni Cd 4 x 1,2V 4Ah

Rated duration time 

1,5h

Time to complete charge 

>14h

Function indication: 

White LED, mains presence

 

Red LED, battery charging

 

Green LED, mains connection ok

4.  Field of application

These accessories are intended for use in potentially explosive atmos-
pheres in Zones 1, 2 in accordance with IEC/EN 60079-10-1 and in Zo-
nes 21,22 in acordance with IEC/EN 60079-10-2. The enclosure mate-
rials used, including any external metal parts, are high quality materials 
that ensure a corrosion resistance and resistance to chemical substan-
ces according to the requirements for use in a ”normal industrial atmos-
phere”, As an example, among others, the following:
 

- Copper free aluminium alloy casting

 

- Plastic powder coating fi nish

 

- Stainless steel

 

- Borosilicate glass

In case of use in an extremely aggressive atmosphere, please consult to 
the manufacturer.

5.  Use/Properties

This light fi tting can be use inside or outside to illuminate areas with po-
tentially  explosive  atmospheres,  may  be  used  only  in  places  with  low 
mechanical impact risk, due to the normal operation in the industrial pro-
cess. The temperature class, explosion group and permissible ambient 
temperature can be found in the tables and technical data.
Light fi ttings suitable for their use as emergency or escape sign luminai-
re. The luminaries can be use as escape sign light fi tting in combination 
with self adhesive pictograms, Optional pictograms can be selected from 
table 2 supplied as optional. 
The data according to sections 2 and 4 shall be taken into account during 
use. Applications other than those described are not permissible without 
a written declaration of consent from EATON Crouse-Hinds Division.
During operation the instructions stated in section 7 of the operating ins-
tructions  shall  be  observed.  The  sole  responsibility  with  respect  to  the 
suitability and proper use of these luminaries lies with the operator.

6.  Installation

The  EN  60079-14,  relevant  national  regulations  and  the  generally  re-
cognized  rules  of  engineering  shall  be  applied  for  the  installation  and 
operation. 
Transport and storage of the luminaries is permitted in the original packa-
ging and specifi ed positions only.

Pay attention when installing, maintaining or repairing the light fi t-
tings,  do  not  damage  the  fi re-fi nish  of  the  glass  surface  by  abra-
sions, sanding, small strokes, etc. that can weaken their mechani-
cal functions.
Intensive sun radiation in areas of high ambient temperatures may 
cause inadmissible temperature rise inside of the luminaries. This 
may  result  a  decrease  in  lifetime  of  the  electronic  ballast  (EVG), 
electronic components and batteries inside of the luminaries. The-
refore  those  luminaries  shall  be  switched  off  during  daytime  by  a 
photocell control.

Earth leakage protection, the earth leakage current of the luminaries is 
normally less than 1 mA, due to this it is suggested non install more than 
30 luminaries for earth leakage switch with sensibility of 30mA.

 

The improper installation and operation of light fi ttings can result in 
the invalidation of the guarantee.

6.1  Mounting

Fixing dimensions are shown in Figure 2 (B). 
Luminaries  are  suitable  for  ceiling,  wall  or  pole  mounting,  the  acces-
sories are not included, see EATON Crouse-Hinds Series catalogue for 
the correct selection of the mounting accessories and self-adhesive pic-
tograms.
The light fi tting may only lie fl at on and be fi xed torsion-free to the faste-
ning points provided for direct assembly. The screws chosen shall fi t the 
fi xing hole and shall not damage the hole (e.g. use of a washer, select the 
correct length, etc.). The number of screws used for fi xing the equipment 
shall correspond to the number of fi xing holes in the light fi tting. 

Special attention shall be paid to the PE connections. 
Warning: Over tightening might damage the light fi tting.

6.2  Opening the device /  Electrical connection

Before opening the light fi tting, it is necessary to ensure that there 
is  no  voltage and  it  must be  allowed  to  cool  down  for 10  minutes 
after switching off.
If it is expressly stated on the label of the luminaire, do not open it 
when an explosive atmosphere is present.

Only luminaires with protection modes “d e marked on the label can be 
opened when an explosive atmosphere is present.
Once the luminaire is opened, the batteries or their parts shall not be ma-
nipulated when an explosive atmosphere is present, this operation can 
only be done when there is no explosive atmosphere present.
The connection of explosion-protected light fi ttings may only be carried 
out  by  specialists.  These  luminaries  shall  be  connected  directly  in  the 
fl ameproof  enclosure  using  certifi ed  fl ameproof  cable  entries,  whereby 
the mounting instructions for the cable entry shall be taken into account 
(see Section 6.3 Cable Entries).

Warning:  In  order  to  establish  the  type  of  protection  “Ex-d  fl ame-
proof “, it is essential to pay attention to the correct mounting of the 
cable and cable entry.

To open a fl ameproof enclosure (see Fig. 3), the interlocking screw, item 
1, in the cover has to be unscrewed. The cover, item 2, can then be re-
moved from the luminary by turning it anticlockwise.

Warning: The cover shall be safeguarded against falling off.

 

To maintain the explosion protection, conductors shall be connected with 
special care. 
The insulation shall reach up to the terminal. The conductor itself shall 
not be damaged. 
The minimum and maximum conductor cross sections that can be con-
nected shall be observed, see point 3 technical data. All screws and/or 
nuts of connection terminals, including those not in uses, shall be tighte-
ned down securely. Torque = 0,7Nm.

Excessive tightening can affect the connection.

Содержание CROUSE-HINDS EE 11 PL Series

Страница 1: ...Y DO 9 R HNVSOXDW FLMDV D D YDUDW SLHSUDV YDOVWV DWELO JDM J D DQ0 DO 1 J0 D QD MRQDOL WDJ KRP PLQJ DQG LU UD DQW WD RR I SDMML KRP QRRG DNHOLMN NDQ YHUWDOLQJ YD GH H JHEUXLNVLQVWUXFWLH LQ HHQ DQGHUH...

Страница 2: ...t rmica o la temperatura superficial indi cada en la caratula de la luminaria Las luminarias se har n funcionar seg n lo previsto y nicamen te deben utilizarse cuando no existan defectos est n limpia...

Страница 3: ...e los planos y o instrucciones de montaje espec ficas para cada accesorio de montaje Las luminarias deber n fijarse de manera uniforme planas libres de torsi n y s lo en los puntos de fijaci n previst...

Страница 4: ...ento preventivo Como parte de las rutinas de pruebas los dispositivos de disparo por protecci n diferencial deben ser probados dos veces al a o En servicio sobre todo las partes que afectan a la prote...

Страница 5: ...chanical impact risk due to the normal operation in the industrial pro cess The temperature class explosion group and permissible ambient temperature can be found in the tables and technical data Ligh...

Страница 6: ...observed i e IEC EN 60079 17 Before opening the enclosure it is necessary to ensure that the voltage supply has been isolated and should allowed to cool down for 10 minutes after switching off The nec...

Страница 7: ...ection destin s tre utilis s en atmosph res explosibles OJ L 96 29 3 2014 p 309 356 EN 60 079 0 2012 A11 2013 EN 60 079 1 2014 EN 60 079 31 2014 EN 60 598 1 2008 A11 2009 EN 60 598 2 22 1999 A1 2003 A...

Страница 8: ...H A K D R H H J H E O J C H N VLGD RPD ULLJLV D J XYDVW DVMDRPDVHV 9 A A F R 9 R A G J LQGVL HVLQGXVHVW _ a DUYLWWDHVVD WlPlQ Nl L W RKMHHQ NllQ b J RQ VDDWDYLVVD WRLVHOOD 8 Q NLHOHOOl 7HLGlQ 9 A A F...

Отзывы: