Maintenance information

 WARNING 

This equipment requires routine inspection and 

maintenance to ensure proper operation . If it is not 

maintained it may fail to operate properly . Improper 

operation can cause equipment damage and possible 

personal 

injury . 

     

 

 

G105 .1

Maintenance program

A routine maintenance inspection program is required to 

ensure proper operation of the equipment. Detailed service 

records should be recorded in the unit’s inspection and 

maintenance record log. Refer to Tables 1 and 2 for typical 

operating characteristics of the DC Motor Operator Control.

Table 1 .  DC motor operator ratings

Close

max.

(amps)

Open

max.

(amps)

Running load amperage (RLA)

12

12

Lock rotor amperage (LRA)

24

23

In rush

20

19

Table 2 .  DC motor operator-operating characteristics

Close

(secs.)

Open

(secs.)

Min.

Avg.

Max.

Min.

Avg.

Max.

Motor run time

4

12

4

7

Device time (RVAC)

5

5

Device time (VFI)

5

5

Replacement parts

Replacement parts for the DC Motor Operator Control are 

available through the factory Service Department. To order 

parts, contact your Eaton representative for additional 

information and ordering procedures.

10

OPERATION INSTRUCTIONS

   MN285018EN   May 2017

DC motor operator control installation and operation instructions

Содержание COOPER POWER SERIES

Страница 1: ...DC motor operator control installation and operation instructions COOPER POWER SERIES Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 S285 80 1...

Страница 2: ...OSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NO...

Страница 3: ...iliary contacts 2 Simultaneous indication for SCADA 2 Electrical interlocks 2 Control operation LOCAL Mode 3 LOCAL Mode operation 3 LOCAL Mode features 3 Battery charger board 3 Wiring schematic 4 Ins...

Страница 4: ...Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around hig...

Страница 5: ...that the battery is disconnected during storage Quality standards ISO 9001 Certified Quality Management System Control battery storage and charging The 24 Vdc control battery is fully charged prior t...

Страница 6: ...panel With the SCADA switch on REMOTE STATUS and control functions are accessed via the SCADA interface See Figures 4 and 6 Auxiliary contacts One a and one b auxiliary switch contact from the B phas...

Страница 7: ...rupter mechanism via the motor operator STOP YELLOW PUSH BUTTON Stops the motor operated opening or closing action of the selected switch or interrupter mechanism Note N Mechanisms should not be left...

Страница 8: ...Figure 4 Wiring schematic of DC motor operator control 4 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Страница 9: ...agrams supplied with your control for specific information on accessories or special modifications that were supplied at the time of manufacture Dashed wires indicate customer made connections 5 OPERA...

Страница 10: ...h SCADA terminals Select one of several motors Read status of selected motor Operate the selected motor Monitor opening or closing action REMOTE Mode Features All remote features are accessed through...

Страница 11: ...set to the LOCAL position for extended local control operation CLOSE RED PUSH BUTTON Closes the selected switch or interrupter mechanism via the motor operator OPEN GREEN PUSH BUTTON Opens the select...

Страница 12: ...Figure 7 Outline diagram of DC motor operator control 8 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Страница 13: ...onnects the motor to the yellow handle See Figure 11 Translator Tube Figure 10 DC Motor actuator disconnected Note N The actuator and limit switches are adjusted for proper operation prior to shipment...

Страница 14: ...ical operating characteristics of the DC Motor Operator Control Table 1 DC motor operator ratings Close max amps Open max amps Running load amperage RLA 12 12 Lock rotor amperage LRA 24 23 In rush 20...

Страница 15: ...This page intentionally left blank 11 OPERATION INSTRUCTIONS MN285018EN May 2017 DC motor operator control installation and operation instructions...

Страница 16: ...tes Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN285018EN May 2017 KA2048 0406 REV01 Eaton is a registered trademark All trademarks are property of their...

Отзывы: