background image

Installation manual 10679

Effective October 2017

BSPA Type 1 and Type 2 surge protective devices

1. Introduction

1.1 Manual introduction

This installation manual describes the installation 

and operation of the Bussmann™ series BSPA 

surge protective device (SPD). This document 

covers most aspects of installation and operation 

and is a guide only for licensed/qualified 

electricians. If you require further information 

regarding a particular installation, application, 

or maintenance activity, please contact your 

Bussmann series product representative. These 

instructions do not cover all details, variations 

or combinations of the equipment, its storage, 

delivery, installation, check-out, safe operation or 

maintenance. Care must be exercised to comply 

with the prevailing electrical code requirements as 

well as with local, state, and national regulations, 

and the safety practices for this class of 

equipment.
Please read and understand ALL installation and 

operating instructions prior to installation and use 

of this equipment.

1.2 Product overview

The Bussmann series BSPA protects critical 

electrical and electronic equipment from damage 

by voltage transients and surges when properly 

installed. This is done by shunting high energy 

lightning surges (and other transient disturbances) 

away from the equipment being protected. It does 

this in nanoseconds by providing a low impedance 

surge path through thermally protected metal 

oxide varistors (MOV) while supporting power 

frequency voltage. The Type 2 BSPA models 

equipped with EMI filtering are designed to 

protect sensitive equipment from electrical noise. 

Proper installation is critical to ensure the BSPA 

unit operates as intended.
The Type 1 BSPA units are intended for installation 

between the secondary of the service transformer 

and the lineside of the service equipment 

overcurrent protective device; as well as the 

loadside, including watt-hour meter socket 

enclosures intended to be installed without an 

external overcurrent protective device.
The Type 2 BSPA units are intended for installation 

on the loadside of the service equipment 

overcurrent protective device, including branch 

panel locations and functions to protect sensitive 

electronic equipment from damaging voltage 

transients and surges.
The BSPA should be installed as close as possible 

to the equipment to be protected.
BSPA units are available in voltage ratings from 

120 to 600 Vac, surge current ratings from 50 kA 

to 200 kA, and two sizes of NEMA 4X enclosures. 

Enclosure size is determined by voltage and peak 

surge current rating. See the dimension drawings 

for details.
BSPA units are available in five feature options 

covering Form C relays, audible alarms and EMI 

filtering. See section 

12. Catalog numbering 

system

 for details.

Contents

Description Page

1 Introduction    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1
2 Signal words  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
3 Safety precautions   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
4 BSPA catalog number    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
5 BSPA product nameplate   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
6 Installation    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
7 Wiring diagrams   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 6
8 Operation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
9 Specifications   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
10 Maintenance  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
11 Liability   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
12 Catalog numbering system    .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8
13 Voltage configurations per enclosure size    .  .  .  . 9
14 Warranty   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 9

Содержание BUSSMAN Series

Страница 1: ...MOV while supporting power frequency voltage The Type 2 BSPA models equipped with EMI filtering are designed to protect sensitive equipment from electrical noise Proper installation is critical to ensure the BSPA unit operates as intended The Type 1 BSPA units are intended for installation between the secondary of the service transformer and the lineside of the service equipment overcurrent protec...

Страница 2: ... accordance with established safety practices d is trained to render first aid e has received safety training to recognize and avoid the hazards involved f has the skills and knowledge pertaining to the construction and operation of this equipment and its installation IMPORTANT These procedures do not claim to cover all possible details or variations encountered with the installation of a Surge Pr...

Страница 3: ...identifies the unit s specifications and permits specifying any combination to meet requirements BSPA 200 208Y 8 P BSPA Product family Surge rating per phase Voltage system code Options NEMA enclosure For example BSPA unit catalog number BSPA200208Y8P where BSPA BSPA series 200 peak surge current rating 50 kA 200 kA 208Y voltage code and system configuration 8 feature option 1 8 P enclosure type N...

Страница 4: ...S POSSIBLE SEE FIGURE 3 6 2 Panel mounted The preferred mounting of the BSPA is directly to the electrical panel with its integrated male connector hub and the supplied 3 4 trade size conduit locknut Insert the wires through the panel wall being careful not to damage the wire insulation Install the provided locknut and tighten to 20 3 lb in 2 3 N m If the installation requires the NEMA 4X rating i...

Страница 5: ...ncluded 3 4 14 NPS external thread Locknut Mounting feet included 36 inch long wires 3 75 95 3 2 38 60 4 8 48 215 4 10 25 260 4 11 50 292 1 7 48 190 0 9 25 235 0 10 50 266 7 4X Ø 0 223 0 80 20 3 6 67 169 4 0 0747 THK 1 51 38 4 1 51 38 4 6 4 Enclosure mounting feet and dimensions The mounting feet attach to the bottom of the enclosure with the provided screws hardware to mount the feet to wall are ...

Страница 6: ...C typically requiring a 1 pole for single phase systems 2 pole for split phase systems or 3 pole for 3 phase systems 30 A branch circuit breaker to protect BSPA conductors Twist and bind the wires of the BSPA unit tightly together To optimize BSPA performance minimize overall lead length To maximize performance for wire lengths longer than four inches phase wires should be twisted once for each fo...

Страница 7: ... product distributor or Bussmann series product representative as the SPD may be damaged 8 3 Options audible alarm and Form C relay Note Using Form C contacts is optional Connection is not required for the proper BSPA operation The audible alarm and Form C relay are tied to the phase LEDs on the BSPA enclosure If protection to one or more phases is lost the following will occur Single split and 3 ...

Страница 8: ...utlined in appropriate Bussmann Division selling policies or other contractual agreements between the parties This manual is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and the Bussmann Division NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FI...

Страница 9: ...re to give any advice or recommendations by the Bussmann Division shall not constitute any warranty by or impose any liability upon the Bussmann Division AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY FITNESS FOR PURPOSE SOLD PRODUCTIVENESS OR ANY OTHER MATTER In no event shall the Bussmann Division be liable for special or consequential dam...

Страница 10: ...t of Eaton CSA is a registered trademark of the Canadian Standards Group NEC is a registered trademark of the National Fire Protection Association UL is a registered trademark of the Underwriters Laboratories Inc Eaton 1000 Eaton Boulevard Cleveland OH 44122 Eaton com Bussmann Division 114 Old State Road Ellisville MO 63021 United States Eaton com bussmannseries 2017 Eaton All Rights Reserved Prin...

Отзывы: