background image

4

Instruction Booklet 

IB48088

Effective July 2021

Instructions for Eaton’s 7.2 kV Ampgard AR 

(arc resistant motor control center) 

(Compliant to IEEE C37.20.7-2017) 

EATON

 www.eaton.com

1.5 Product description

The controller consists of a non-load break isolation switch, medium 

voltage current-limiting fuses, one or more Type SL vacuum-break 

contactors, a set of current transformers, plus control and protection 

devices.  The isolating switch has a limited make and break rating, 

suitable only for closing and opening limited transformer magnetiz-

ing currents.  For applications other than those indicated, consult 

your Eaton representative.
Each controller occupies all or a portion of a steel structure that may 

also enclose a horizontal bus system to distribute power to two 

or more structures and a vertical bus system to connect individual 

starters to the horizontal bus.  The controllers are configured for 

full-voltage or reduced-voltage starting, reversing or non-reversing 

applications. The controller is available with bolt-in power fuses only.  

The contactor of the controller may have bolted connections or 

stab-in connections.  The contactor is held in place by a set of rails 

mounted in the lower part of the cell.  The current transformers are 

typically mounted immediately after the load-side stabs.  The motor 

load connections are mounted to the left of the power fuses, facing 

forward.
The flow of current through a controller can be described as follows: 

The isolation switch line finger assembly (fixed portion) mounted at 

the back of the controller rear panel serves to connect to the isola-

tion switch stab (removable portion).  When the isolation switch is 

closed, the power flows from the isolation switch line finger assem-

bly to the stab and then through the flexible shunt(s) to the upper 

fuse mounting.  The upper fuse mounting serves the purpose of 

placing the power fuses at the back of the rear panel.  The top of the 

fuse is bolted to the upper fuse mounting behind the service barrier.  

The bottom end of the power fuses are connected to the lower fuse 

mounting that contain the line-side bolted or stab-in connections for 

the main contactor.  These connections serve to connect to the line 

finger assemblies of the main contactor.  With the main contactor 

energized, power flows through the contactor’s vacuum interrupters 

to the contactor load fingers, which are engaged on to the contactor 

load-side stabs.  Medium voltage cables connect the contactor load-

side stabs to the motor load connections.

Figure 2. Components.

1.5.1 Isolation switch

The Ampgard AR isolation switch is compartmentalized to prevent 

phase-to-phase arcing during a fault event.  The switch features are 

described in IB48041 (400 A) and IB48043 (800 A) (see 

Figure 2

).

1.5.2 Power fuses

Ampgard AR controllers are supplied with Eaton type CLS or HLE 

current-limiting power fuses.  The controller includes bolt-in, current-

limiting power fuses.  All fuses include an indicator that pops up 

when the fuse has blown.  Optional blown fuse trip bar assembly 

can be mounted on the controller isolation switch and is wired to 

trip the controller off-line in the event of a blown fuse (see 

Figure 3

).

Figure 3. Optional blown fuse trip bar assembly.

Ampgard AR power fuses are installed behind the service barrier. 

The service barrier must be installed during normal operation to 

maintain the arc resistant rating of the equipment.
To access the power fuses, follow the below steps:

1.  Remove the six bolts shown circled in 

Figure 4 

and set them 

aside for later reassembly.

2.  Tilt the service barrier towards you from the top using the two 

black handles.  The service barrier will tilt towards you about 

30 degrees before it is stopped by the phase barriers sticking 

through it at the bottom.

3.  Lift the service barrier up towards you and at the same time 

angling it away from the isolation switch interlock rod.

4.  Set it aside safely.  The service barrier weighs approximately 20 

lbs (9.07 kg).

Blown fuse 

Indicator assembly

Isolation 

switch

Power fuse 

service barrier

Handle 

mechanism

Control 

terminal 

block

Motor load 

connection

Contactor

Содержание Ampgard AR

Страница 1: ...istant MVCC and Eaton VacClad switchgear 13 Section 5 Duct and plenum installation 17 5 1 Receiving 17 5 2 Handling 17 5 3 Access to equipment 17 5 4 Exhaust duct 17 5 5 Medium voltage cableways 20 5...

Страница 2: ...starters and reduced voltage starters such as reactor auto transformer and solid state starters Equipment qualified as arc resistant in accordance to IEEE C37 20 7 2017 is intended to provide an addi...

Страница 3: ...continuous current Rated short circuit current withstand 2 second Dielectric withstand Impulse kV rms Amperes Amperes kV rms kV peak Amperes kA rms sym 7 2 1 400 400 18 2 60 1000 1200 2000 3000 50 2 4...

Страница 4: ...the upper fuse mounting behind the service barrier The bottom end of the power fuses are connected to the lower fuse mounting that contain the line side bolted or stab in connections for the main cont...

Страница 5: ...uses and pull the blown fuse indicator down to rest on top of the fuse Ferrell You will hear a click 12 Reposition the service barrier and reinstall the six bolts Tighten until the lock washers are fl...

Страница 6: ...for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 7 Low voltage control compartment Figure 8 Sealing gaskets Isolation switch...

Страница 7: ...an incoming line section may include vertical bus drops to connect the incoming line cables Options for both the top and bottom entry motor cables are available Also included in the main bus enclosur...

Страница 8: ...ment particular to its arc resistant enclosure This document must be used in conjunction with the following instructions specific to the type of starter being installed IB48041 AMPGARD 400 A Motor Sta...

Страница 9: ...t mechanical interlocks Therefore a final inspection is essential before energizing Figure 11 Location of lifting plates After the section has been moved into installation position remove the hooks an...

Страница 10: ...h arc resistant MV MCC vertical section mounting hole location must be considered Consult a licensed structural or civil engineer prior to selecting a mounting system if a system other than that recom...

Страница 11: ...e following ways shown below Figure 13 Exhaust duct exiting the plenum Figure 14 Exhaust duct manifold side s ONLY Figure 15 Closed coupled with Eaton VacClad switchgear Back to back B2B Figure 16 Clo...

Страница 12: ...e July 2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 14 50 kA arc resistant line up Shown with dual exha...

Страница 13: ...ion must be attached to the switchgear before the plenums are installed Follow the instructions below for coupling the Ampgard AR lineup to the VacClad switchgear 1 Position the Ampgard AR lineup next...

Страница 14: ...E C37 20 7 2017 EATON www eaton com 5 Make all bus splice connections Torque per Table 6 6 Cover all bus connections with the supplied bus boots 7 Replace the covers that were removed in order to acce...

Страница 15: ...July 2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 17 50 kA arc resistant line up Shown with close coup...

Страница 16: ...2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 18 50 kA arc resistant line up Shown with close coupled w...

Страница 17: ...ach shipping group Using a four leg bridle sling chain place one hook through each of the four eyes to lift and move the group No leg of the sling shall be at an angle greater than 45 degrees from the...

Страница 18: ...y be used however the support hardware may not be drilled or screwed into the duct Arc duct hanger assembly 69C4455G01 is available from Eaton as shown in the Figure 21 The duct must have a downward s...

Страница 19: ...uction Booklet IB48088 Effective July 2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 21 Exhaust duct comp...

Страница 20: ...slots Secure it in place with hardware kit 25A4361G12 see Figure 22 The low voltage cableway is built into the plenum It will need two screws and two flat washers from hardware kit 25A4361G12 to compl...

Страница 21: ...the bolts until all the hardware and plenum assemblies are in place Follow the steps below to install the plenum and its accessories 1 Remove the hardware from the front and rear flange of the main bu...

Страница 22: ...C37 20 7 2017 EATON www eaton com Figure 24 Installing the plenums 4 Install the reinforcement angle parts as shown in Figure 25 and Figure 26 5 Use hardware kit 25A4361G10 for the plenum section fro...

Страница 23: ...ctive July 2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 25 Installing the reinforcement angles Figure 2...

Страница 24: ...op of the gear and then lift the duct collar inside the plenum and install it immediately before installing additional plenum assembly sections e Use 1 4 in 20 bolts lock washers flat washers and nuts...

Страница 25: ...to the top of the plenum 15 Align all the holes of the cableway cutout in the plenum roof with the holes on top flanges of the cableway 16 Only use the middle holes on each side to anchor the cablewa...

Страница 26: ...ter Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 29 Holes used to attach the MV plenum conduit to the plenum roof 19 Install the arc gas deflector parts as shown in Figure 30 Use hardwar...

Страница 27: ...rd AR vents the hot arc gases produced away from designated areas and the personnel that could be present Personnel cannot be permitted in the arc gas vent area during normal operation The following f...

Страница 28: ...ant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Figure 32 Additional minimum requirements for the arc gas vent area Table 7 Duct end assembly requirements Dimension Duct e...

Страница 29: ...install a 1 4 in 20 nut with locking hardware on the backside of the screw and torque per Table 6 Periodically inspect the air filter on the duct if present and replace if soiled or clogged Section 8...

Страница 30: ...30 Instruction Booklet IB48088 Effective July 2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Notes...

Страница 31: ...31 Instruction Booklet IB48088 Effective July 2021 Instructions for Eaton s 7 2 kV Ampgard AR arc resistant motor control center Compliant to IEEE C37 20 7 2017 EATON www eaton com Notes...

Страница 32: ...ther contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTAB...

Отзывы: