Page 46
614-20306-00 - 9SX 0-6 KVA EMEA_EN
8.
Pull out the plastic handle of the battery pack,
and slide the pack out slowly on to a
fl
at and
stable surface. Use two hands to support
the battery pack. See "Recycling the used
equipment" on page 49 for proper disposal.
9.
Verify that the replacement batteries have the
same rating as the batteries being replaced.
10.
Put the new battery pack into the UPS. Push
the battery pack
fi
rmly to ensure a proper
connection.
11.
Reassemble in the reverse order.
12.
Continue to “Testing new batteries” on page
49.
13.
Reset the 4 years Life Cycling Monitoring
(LCM): Control > Reset battery life.
• Replacing the internal battery - TOWER 5-6KVA
The internal battery is heavy. Use caution when handling the heavy batteries.
The internal batteries are located behind the UPS front cover. The internal batteries are packaged together as
one unit for easier handling.
To replace the batteries in the UPS:
1
. Remove the UPS front cover.
To remove the cover:
Remove
the
2
fi
xing screws on the bottom of
the cover.
Push upon the bottom of the cover and pull the
cover toward you to unclip it from the cabinet.
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.