Page 37
614-00205-01_EN
ENGLISH
9. UPS maintenance
•
Replacing the UPS internal battery
The internal battery is heavy. Use caution when handling the heavy batteries.
Description
Weights (lb/
kg
)
9PX 8K SP internal battery
67.3 /
30.5
9PX 10K SP internal battery
67.3 /
30.5
To replace the battery pack:
• Remove the two center cover of the front panel.
• Remove the four screws to remove the bottom front panel.
• Remove the two screws to pull out the metal protection cover of the battery.
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
• Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable
surface. Use two hands to support the battery pack.
See "Recycling the used equipment" on page 39 for proper disposal.
• Verify that the replacement batteries have the same rating as the batteries being replaced.
• Put the new battery pack into the UPS. Push the battery pack firmly to ensure a proper
connection.
• Screw back the metal protection cover and the front panel, then clip the center cover.
• Continue to "Testing new batteries" on page 38.