Page 14
614-00205-01_EN
3. Installation for 9PX 8K SP and 9PX 10K SP
3.6 Connecting the internal battery
Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment
and void your warranty. Do not connect the UPS to utility until installation is completed.
This step requires two service personnel, the UPS and internal battery are heavy.
Description
Weights (lb/
kg
)
9PX 8K SP/9PX 10K SP without internal battery
91 /
41
9PX 8K SP/9PX 10K SP internal battery
67.3 /
30.5
• Mount the UPS on rack.
• Remove the center cover of the front panel.
• Remove the four screws to open the front panel.
• Remove the three screws to pull out the metal protection cover of the battery.
• Put the battery pack, screw back the metal protection cover, connect the battery and put back the
front panel, then clip the center cover.
Battery connectors may be coupled
to either battery pack.
A small amount of arcing may occur when connecting the internal batteries. This is normal and will
not harm personnel. Connect the cables quickly and firmly.
Содержание 9PX10KSP
Страница 48: ...Page 48 614 00205 01_EN...
Страница 96: ...Page 48 614 00205 01_FR...
Страница 144: ...P gina 48 614 00205 01_ES...
Страница 192: ...p gina 48 614 00205 01_PT...