TROUBLESHOOTING
Eaton 9910 UPS and EBM User's Guide
S
P-164000005 Rev 2
62
Typical Alarms and Conditions
Table 15 describes the typical alarms and conditions.
Table 15. Typical Alarms and Conditions
Alarm or Condition
Possible Cause
Action
The UPS does not provide or
indicate the expected backup time.
The batteries need charging or
service.
Apply utility power for 48 hours to charge
the batteries. If the condition remains,
contact your service representative.
Power is not available at the UPS
output receptacles.
The UPS is in Standby mode.
Supply power to the connected equipment
by pressing the on/off button until the status
summary screen is displayed on the UPS
front panel.
The UPS does not start. (The LCD
is off.)
The power is not connected.
Check the power cord connections.
3000 VA Models:
The battery is
disconnected.
Verify that the battery is connected. If the
condition remains, remove utility power,
disconnect the battery, reconnect the
battery, then apply utility power.
3000 VA Models:
The batteries
need charging or service.
Apply utility power for 48 hours to charge
the batteries. If the condition remains,
contact your service representative.
The UPS operates normally, but
some or all of the protected
equipment is not on.
The equipment is not connected
correctly to the UPS.
Verify that the equipment is connected to
the UPS receptacles. Also verify that the
load segment is on.
A communication port or an
optional communication card does
not operate.
The communication cable is not
compatible.
Verify that the correct communication cable
is connected to the port or card.
Battery test did not run or was
interrupted.
One of the conditions listed in
“Running Automatic Battery Tests”
on page 34 was not present.
Resolve the condition, and then restart the
test.
UPS on Battery
(Event 168)
No Alarm
NOTE
The utility alarm that
caused the transfer to Battery
mode sounds its alarm.
A utility power failure has
occurred, and the UPS is in Battery
mode.
The UPS is powering the equipment with
battery power. Prepare the equipment for
shutdown.
Содержание 9910
Страница 1: ...Powerware Series Eaton 9910 UPS and EBM User s Guide ...
Страница 2: ......
Страница 3: ...Powerware Series Eaton 9910 UPS and EBM User s Guide ...
Страница 26: ...INSTALLATION Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 18 ...
Страница 44: ...OPERATION Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 36 ...
Страница 60: ...UPS MAINTENANCE Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 52 ...
Страница 75: ......
Страница 76: ... P 1640000052 P 164000005 2 ...