UPS MAINTENANCE
Eaton 9910 UPS and EBM User's Guide
S
P-164000005 Rev 2
42
Replacing the Internal Batteries (3000 VA Models)
NOTE
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
With the hot‐swappable battery feature, UPS batteries can be replaced
easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the batteries:
1.
Press and hold the on/off button until the long beep ceases
(approximately 3 seconds), and then disconnect the UPS.
2.
Wait 60 seconds while the internal processor shuts down before
you disconnect the battery.
To replace the UPS internal batteries:
C
A
U
T
I
O
N
S
Read and understand all warnings and cautions listed in “Safety Warnings” on page 5.
S
Pull the batteries out onto a flat, stable surface. The batteries are unsupported when you
pull them out of the UPS.
S
The UPS batteries are heavy (see page 54). A minimum of two people are required to lift
the batteries into the UPS chassis.
1.
Remove the UPS front cover. Press the two side latches toward
each other to release the front cover, and pull off the cover.
Figure 7. Removing the UPS Front Cover
Содержание 9910
Страница 1: ...Powerware Series Eaton 9910 UPS and EBM User s Guide ...
Страница 2: ......
Страница 3: ...Powerware Series Eaton 9910 UPS and EBM User s Guide ...
Страница 26: ...INSTALLATION Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 18 ...
Страница 44: ...OPERATION Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 36 ...
Страница 60: ...UPS MAINTENANCE Eaton 9910 UPS and EBM User s Guide S P 164000005 Rev 2 52 ...
Страница 75: ......
Страница 76: ... P 1640000052 P 164000005 2 ...