Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
79
Figure 37. Wire Tie Anchors
Wire Tie
Anchors
Table 21. Building Alarm Connections and Wire Terminations
Termi-
nal
Name
Description
Recommended
Minimum
Wire Size
Size of
Pressure
Termination
Tightening
Torque
10
Building Alarm 1
Input: Programmable UPS
alarm, activated by a remote
dry contact closure
Twisted Pair
Wires #18 AWG
#14 #30 AWG
2 lb in
(0.22-0.25 Nm)
9
Building Alarm 1 Return
8
Building Alarm 2
7
Building Alarm 2 Return
6
Building Alarm 3
5
Building Alarm 3 Return
4
Building Alarm 4
3
Building Alarm 4 Return
2
Building Alarm 5
1
Building Alarm 5 Return