INSTALLATION
EATON
Powerware
®
9135 Two−in−One UPS (5000/6000 VA) User’s Guide
S
164201726 Rev 1
www.powerware.com
37
RPO Installation
Installation of the RPO function must be carried out in compliance with
applicable regulations. The cable is not included.
In order to fully de−energize devices and the Powerware 9135 with the
RPO port, it is necessary to:
S
Use a two−position switch (normally−open or normally−closed contact
and held more than one second).
S
Connect this RPO switch to a device that trips all breaker(s) located
upstream
(1)
and downstream
(2)
the Powerware 9135 UPS. This can
be achieved by means of a shunt trip:
−
(1)
If not, the output devices could be powered again through static
switch when the two−position switch is released.
−
(2)
If not, the output devices will remain powered several seconds
after the RPO activation.
NOTE
The internal batteries will remain connected to the power module after RPO
activation.
RPO Contact Normally−Open
RPO Contact Normally−Closed
5 Vdc to 27 Vdc
5 Vdc to 27 Vdc
RJ−12 (6p6c)
RJ−12 (6p6c)
Figure 19. RPO Communication Port
S
Signal:
−
Activation voltage:
5 Vdc to 27 Vdc
−
Current:
10 mA maximum