620-00082-01-au (en)
ENGLISH
2. Presentation
Description
Available settings
Default settings
In/Out settings
Load segments
- Auto shutdown
delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage, authorises
to keep some equipment running
while turning off other equipment.
This feature allows to save battery
power.
Group 1: Disable
Group 2: Disable
Overload pre-
alarm
[10 %] [15 %] [20 %] ... [100 %]
[105 %]
Gives a warning when a predefined
critical percentage of load is
reached.
[105 %]
ON/OFF settings
Cold start
[Disable] [Enable]
Enables the product to be started
on battery power.
First cold start always disabled.
Enable
Forced reboot
[Disable] [Enable]
If mains recover during a shutdown
sequence:
- if enabled, shutdown sequence will
complete and wait 10 seconds prior
to restart
- if disabled, shutdown sequence will
not complete and restart will occur
immediately.
Enable
Auto restart
[Disable] [Enable]
Enables the product to restart auto-
matically when mains recovers
after a complete battery discharge.
Enable
Energy saving
[Disable] [Enable]
If enabled, UPS will shutdown after
5min of back-up time, if no load is
detected on the output.
Disable
Sleep mode
[Disable] [Enable]
If disabled, LCD and communica-
tion will turn OFF immediately after
UPS is OFF.
If enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
Disable
Remote command [Disable] [Enable]
If enabled, shutdown or restart
commands from software are
authorised.
Enable
RPO delay
[0 s] [1s ] [2 s]...[180 s]
Delays remote power off command
[0 s]
Battery settings
Automatic battery
test
[No test] [Every day] [Every week]
[Every month]
Available only if battery charge
mode is set to constant charge.
Every week
(in constant charge,
otherwise following ABM
battery test method)
Low battery warn-
ing
[1 %] [2 %] ... [100 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
20 %
Restart battery
level
[1 %] [2 %] ... [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
0 %
Battery charge
mode
[ABM cycling] [Constant charge]
ABM cycling
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep
discharge by adapting end of
back-up time voltage threshold.
Yes