Green/Red LED alter- 
native flashes every 
0.5 second and audio 
alarm beeps every 1.5 

second. 

 

The connected loads are 
exceed the UPS capacity or 
Battery fault 

The connected loads are exceed 
the UPS capacity, remove some 
noncritical loads or check if some 
loads are failed. 

Red LED is on and the 
audio alarm beeps 
continuous. 

A fan fault has occurred on 
the UPS. The UPS outlets are 
no longer supplied. 

Check if the fan is stopped, if 
no, please contact your service 
representative. 

Red LED is on and the 
audio alarm beeps 
continuous. 

An internal fault has occurred 
on the UPS. The UPS outlets 
are no longer supplied. 

Contact your service 
representative. 

USB communication 
fails. 

Cable connection may be 
defective. 

Re-connect the USB cable, if still 
not available. Contact your service 
representative. 

 

7.1

 

Service and support 

If you have any question or problem with the UPS, call Eaton or your local ser- vice 
representative  in  your  country  /  region.  Please  have  the  following  information 
ready when you call for service: 

 

Model number 

 

Serial number 

 

Firmware version number 

 

Date of failure or problem 

 

Symptoms of failure or problem 

 

Customer return address and contact information 

If repair is required, you will be given a Returned Material Authorization (RMA) 
number. This number must appear on the outside of the package and on the Bill 
Of Lading (if applicable). Use the original packaging or request packaging from the 
Help Desk or distributor. Units damaged in shipment as a result of improper pack- 
aging are not covered under warranty. A replacement or repair unit will be shipped 
freight prepaid for all warrantied units. 

For critical applications, immediate replacement may be available. Call the 
Help Desk for the dealer or distributor nearest you. 

Содержание 5E700UD-KR

Страница 1: ...Eaton 5E Advanced User Guide 5E700UD KR 5E1200UI KR 5E1600UI KR 5E2200UI KR Copyright 2023 EATON All rights reserved DSD 5E2209 English...

Страница 2: ......

Страница 3: ...ort 9 5 Operation 10 5 1 Start up and normal operation 10 5 2 Starting the UPS on battery 11 5 3 UPS shutdown 11 5 4 Operating modes 12 5 5 Return of AC input power 12 6 UPS maintenance 13 6 1 Equipme...

Страница 4: ......

Страница 5: ...sk of energy or electrical shock or burn from high short circuit current Observe proper precaution Batteries may contain HIGH VOLTAGE and CORROSIVE TOXIC and EXPLOSIVE substances Information advice he...

Страница 6: ...protection Eaton has implemented an environmental protection policy Products are devel oped according to an eco design approach 2 1 1 Substances This product does not contain CFC and HCFC This produc...

Страница 7: ...ons concerning batteries The battery may be removed to comply with regulations and in view of correct disposal 2 2 Benefits The Eaton 5E uninterruptible power system UPS protects your sensitive electr...

Страница 8: ...escription UPS Weights kg lbs Dimentions mm inch D x W x H 5E700UD KR 4 3 9 5 288 x 100 x 148 11 5 x 3 9 x 5 8 5E1200UI KR 8 2 18 2 330 x 133 x 180 13 0 x 5 2 x 7 1 5E1600UI KR 8 9 19 6 330 x 133 x 18...

Страница 9: ...5 1 1 3 2 2 5E1200UI KR 5E1600UI KR 5E2200UI KR 3 2 Front panel 3 3 Rear panel 1 USB communication port 2 ON OFF Button 3 UPS status LED 1 AC Input 3 Fan 2 AC Output KR 2 3...

Страница 10: ...aled damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative Check the battery recharge date on the sh...

Страница 11: ...located on the back of the UPS correspond to the AC power source and the true electrical consumption of the total load Connect the UPS to the AC power source with cable through a wall outlet equipped...

Страница 12: ...s Backup Protected outlets Plug critical equipment computer monitor modem etc to the backup pro tected outlets providing battery backup power taking care not to exceed the rated current indicated in a...

Страница 13: ...soon as the AC cord is plugged in These are not affected by ON OFF button 4 4 USB COM port Connect the UPS to the computer using the USB cable Enhance your purchase by downloading the monitoring softw...

Страница 14: ...buzzer temporarily when there is a fault occur or battery test fail 2 UPS on off Push the button for 2s then to power on off the UPS 3 Silence mode Let UPS working in the standby mode then to push the...

Страница 15: ...tandby mode to Battery mode The indicator blinking and the buzzer snooze The UPS supplies power to your equipment 2 Check the UPS front panel display for active alarms or notices besides the Bat tery...

Страница 16: ...low while in Battery mode the audible alarm beeps faster This warning is approximate and the actual time to shutdown may vary signifi cantly gracefully shutdown all applications on connected equipmen...

Страница 17: ...temperature below 10 C 6 2 Storing the equipment If you store the equipment for a long period recharge the battery every 6 months by connecting the UPS to utility power The internal batteries charge...

Страница 18: ...eries and must be disposed of properly For more information con tact your local recycling reuse or hazardous waste center Do not discard waste electrical or electronic equipment WEEE in the trash For...

Страница 19: ...tlets are not supplied with power or the UPS cannot be turn on after pressing the button The ON OFF Button is not pressed or the ON OFF but ton is pressed too briefly Press the button continuously for...

Страница 20: ...service representative 7 1 Service and support If you have any question or problem with the UPS call Eaton or your local ser vice representative in your country region Please have the following infor...

Страница 21: ...lation Boost1 Vin 1 2 Boost2 Vin 1 4 Buck Vin 0 857 10 15 Efficiency 95 60 Frequency regulation Same as input 1 Hz Nominal output 220 230 240V Frequency Follows input frequency 50 60Hz Output overload...

Страница 22: ...3 Performance EMC Emissions CISPR32 Class A IEC EN 61000 3 2 Flickers IEC EN 61000 3 3 Harmonics This is a category C2 Class A UPS product In a residential environ ment this product may cause radio in...

Страница 23: ...131 F without battery Relative humidity Storage 0 93 non condensing Operation 0 85 non condensing Operating altitude 2000 m Transit altitude Up to 10 000 meters 32 808 ft above sea level Audible noise...

Страница 24: ...connected to the UPS output Normal mode The normal UPS operating mode in which the AC source supplies the UPS which in turn provides AC power to the connected loads Normal AC source Normal source of...