Troubleshooting 

The Eaton 5E is designed for reliable, autonomous operation while providing you 
with notifications and alerts whenever a 
potential operational or performance issue occurs. 
Usually the alarms shown by the control panel do not mean that the output power 
is affected. Instead, they are preventive alarms intended to alert the user. 

 

Events are silent status information that are recorded into the Event log. Exam- 
ple = “AC freq in range”. 

 

Alarms are recorded into the Event log and displayed on the LCD status screen 
with the logo blinking. Some alarms may be announced by a beep every 3 sec- 
onds. Example = “Battery low”. 

 

Faults are announced by a continuous beep and red LED, recorded into the Fault 
log and displayed on the LCD with a specific message box. Example = Out. short 
circuit. 
Use the following troubleshooting chart to determine the UPS alarm condition. 

 

Conditions 

Possible cause 

Action 

The UPS outlets are 
not supplied with 
power or the UPS 
cannot be turn on 
after pressing the 

button 

 

The ON/OFF Button is not 
pressed or the ON/OFF but- 
ton is pressed too briefly. 

 

Press the button continuously for 
more than 2 seconds and check 
that LED turns to green. 

The connected devic- 
es are not supplied 
when AC power fails. 

 

The devices are not connect- 
ed good to the UPS outlets . 

 

Check the cables and reconnect 
the devices to the UPS outlets. 

Green LED flashes 
every 1 second and 
audio alarm beeps 
every 5 seconds. 

The UPS frequently operates 
on battery power because 
the AC power source is of 
poor quality. 

 

Have the electrical installation 
checked by a professional or use 
another wall outlet. 

Green LED flashes 
every 1 second and 
audio alarm beeps 
every 1.5 second. 

 

UPS operates on battery 
power with a low battery 

 

The actual time to shutdown may 
vary significantly, prepare your 
equipment for shutdown. 

 

Battery discharging 
time diminishes 

 

Battery not yet been fully 
charged or overloaded 

Keep UPS connected to utility 
power persistently for more than 
6 hours to recharge the batteries. 

Or remove some noncritical loads. 

Содержание 5E700UD-KR

Страница 1: ...Eaton 5E Advanced User Guide 5E700UD KR 5E1200UI KR 5E1600UI KR 5E2200UI KR Copyright 2023 EATON All rights reserved DSD 5E2209 English...

Страница 2: ......

Страница 3: ...ort 9 5 Operation 10 5 1 Start up and normal operation 10 5 2 Starting the UPS on battery 11 5 3 UPS shutdown 11 5 4 Operating modes 12 5 5 Return of AC input power 12 6 UPS maintenance 13 6 1 Equipme...

Страница 4: ......

Страница 5: ...sk of energy or electrical shock or burn from high short circuit current Observe proper precaution Batteries may contain HIGH VOLTAGE and CORROSIVE TOXIC and EXPLOSIVE substances Information advice he...

Страница 6: ...protection Eaton has implemented an environmental protection policy Products are devel oped according to an eco design approach 2 1 1 Substances This product does not contain CFC and HCFC This produc...

Страница 7: ...ons concerning batteries The battery may be removed to comply with regulations and in view of correct disposal 2 2 Benefits The Eaton 5E uninterruptible power system UPS protects your sensitive electr...

Страница 8: ...escription UPS Weights kg lbs Dimentions mm inch D x W x H 5E700UD KR 4 3 9 5 288 x 100 x 148 11 5 x 3 9 x 5 8 5E1200UI KR 8 2 18 2 330 x 133 x 180 13 0 x 5 2 x 7 1 5E1600UI KR 8 9 19 6 330 x 133 x 18...

Страница 9: ...5 1 1 3 2 2 5E1200UI KR 5E1600UI KR 5E2200UI KR 3 2 Front panel 3 3 Rear panel 1 USB communication port 2 ON OFF Button 3 UPS status LED 1 AC Input 3 Fan 2 AC Output KR 2 3...

Страница 10: ...aled damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative Check the battery recharge date on the sh...

Страница 11: ...located on the back of the UPS correspond to the AC power source and the true electrical consumption of the total load Connect the UPS to the AC power source with cable through a wall outlet equipped...

Страница 12: ...s Backup Protected outlets Plug critical equipment computer monitor modem etc to the backup pro tected outlets providing battery backup power taking care not to exceed the rated current indicated in a...

Страница 13: ...soon as the AC cord is plugged in These are not affected by ON OFF button 4 4 USB COM port Connect the UPS to the computer using the USB cable Enhance your purchase by downloading the monitoring softw...

Страница 14: ...buzzer temporarily when there is a fault occur or battery test fail 2 UPS on off Push the button for 2s then to power on off the UPS 3 Silence mode Let UPS working in the standby mode then to push the...

Страница 15: ...tandby mode to Battery mode The indicator blinking and the buzzer snooze The UPS supplies power to your equipment 2 Check the UPS front panel display for active alarms or notices besides the Bat tery...

Страница 16: ...low while in Battery mode the audible alarm beeps faster This warning is approximate and the actual time to shutdown may vary signifi cantly gracefully shutdown all applications on connected equipmen...

Страница 17: ...temperature below 10 C 6 2 Storing the equipment If you store the equipment for a long period recharge the battery every 6 months by connecting the UPS to utility power The internal batteries charge...

Страница 18: ...eries and must be disposed of properly For more information con tact your local recycling reuse or hazardous waste center Do not discard waste electrical or electronic equipment WEEE in the trash For...

Страница 19: ...tlets are not supplied with power or the UPS cannot be turn on after pressing the button The ON OFF Button is not pressed or the ON OFF but ton is pressed too briefly Press the button continuously for...

Страница 20: ...service representative 7 1 Service and support If you have any question or problem with the UPS call Eaton or your local ser vice representative in your country region Please have the following infor...

Страница 21: ...lation Boost1 Vin 1 2 Boost2 Vin 1 4 Buck Vin 0 857 10 15 Efficiency 95 60 Frequency regulation Same as input 1 Hz Nominal output 220 230 240V Frequency Follows input frequency 50 60Hz Output overload...

Страница 22: ...3 Performance EMC Emissions CISPR32 Class A IEC EN 61000 3 2 Flickers IEC EN 61000 3 3 Harmonics This is a category C2 Class A UPS product In a residential environ ment this product may cause radio in...

Страница 23: ...131 F without battery Relative humidity Storage 0 93 non condensing Operation 0 85 non condensing Operating altitude 2000 m Transit altitude Up to 10 000 meters 32 808 ft above sea level Audible noise...

Страница 24: ...connected to the UPS output Normal mode The normal UPS operating mode in which the AC source supplies the UPS which in turn provides AC power to the connected loads Normal AC source Normal source of...

Страница 25: ......

Отзывы: