I.B. 32-255-1G
Page 44
Effective 12/02
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
6-11 TROUBLESHOOTING CHART (Continued Next Page)
Fails To Close
• Closing Sound
• Pole Shaft
but no close
(Not open fully)
• Trip Latch Reset Spring
(Damaged or Missing)
• Trip Bar-D Shaft
(Fails to remain reset)
• Trip Latch-Hatchet
(Fails to remain reset)
• Trip Floor Tripper
(Fails to remain reset)
• Close Latch
(Binding)
• Close Latch Roller
(Binding)
• Trip Circuit Energized
Undesirably Closes
• Control Circuit
• Close Circuit
(CS/C Getting Shorted)
• Mechanism
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
Fails To Trip
• No Trip Sound
• Control Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• Trip Mechanism
• Trip Clapper
(Jammed)
Содержание 50VCPW-ND250
Страница 2: ......
Страница 8: ...I B 32 255 1G Page viii Effective 12 02 ...