ROBLEM SOLVING

 

Irregular functioning of the UPS is very often not an indication of a fault but due simply to trivial problems, 
minor difficulties or carelessness. 
We therefore recommend that you refer to the table below which gives a summary of useful information to 
solve the most common problems. 
 
 

PROBLEM 

POSSIBLE CAUSE 

SOLUTION 

 

GENERAL SWITCH NOT 

PRESSED 

Press the general switch located on the front panel. 

THE BATTERY PACK 

CONNECTOR IS 

DISCONNECTED 

Connect the battery pack connector by following the 
instructions set out in the paragraph “REPLACING 
THE BATTERY PACK”. 

NO CONNECTION TO THE  

ELECTRICITY MAINS 

Check the connection to the electricity mains. 

MAINS VOLTAGE FAILURE  

(BLACK-OUT) 

Check the presence of the electricity mains voltage. 

THE DISPLAY DOES NOT 

SWITCH ON 

UPSTREAM PROTECTION 

TRIGGERED 

Reset the protection. 
WARNING: Check that there is no overload in output 
to the UPS. 

 

THE UPS IS IN STAND-BY 

MODE 

Press the “ON” key located on the front panel to power 
the loads. 

STAND-BY OFF MODE HAS 

BEEN SELECTED

 

The mode has to be changed. 
The STAND-BY OFF mode (back-up) in fact only 
powers the loads in the event of a black-out. 

THE DISPLAY IS ON BUT 

THE LOAD IS NOT 

POWERED  

NO CONNECTION TO THE 

LOAD 

Check the connection to the load. 

 

UPSTREAM PROTECTION 

TRIGGERED 

Reset the protection. 
WARNING: Check that there is no overload in output 
to the UPS. 

THE UPS IS OPERATING 

FROM BATTERY EVEN 

THOUGH THE MAINS 

VOLTAGE IS PRESENT  

THE INPUT VOLTAGE IS 

OUTSIDE THE ALLOWED 

TOLERANCE FOR 

OPERATION FROM MAINS 

Problem dependent on the mains. Wait for the input 
mains to return within tolerance. The UPS will 
automatically go back to operation from mains.  

 

THE UPS DOES NOT 

SWITCH ON AND THE 

DISPLAY SHOWS ONE OF 

THESE CODES:

 A06, A08 

THE TEMPERATURA OF THE 

UPS IS LOWER THAN 0°C 

Check the temperature of the environment where the 
UPS is located; if it is too low, bring it to above the 
minimum threshold (0°C). 

 

THE DISPLAY SHOWS THE 

CODE:

 A11 

INPUT RELAY BLOCKED 

The fault does not cause any particular malfunctions. If 
the problem should occur again on a subsequent start-
up, contact the support service centre. 

Содержание 5000 VA

Страница 1: ...Uninterruptible Power Supply ON LINE MULTISTANDARD 5000 VA 6000 VA Manuale d uso User s Manual Bedienungsanleitung Manuel d utilisateur Manual de Usuario...

Страница 2: ......

Страница 3: ...s into fire they may explode Do not try to open the battery packs they do not require any maintenance Furthermore the electrolyte is dangerous if it comes into contact with the skin or the eyes and ma...

Страница 4: ...43 GB USER S MANUAL GB...

Страница 5: ...HOROUGHLY READING THIS MANUAL The manual contains detailed instructions on how to use and install the UPS For information on using and getting the best performance from your UPS this manual should be...

Страница 6: ...54 DISPLAY PANEL INDICATIONS 55 UPS status indicators 55 Measurements display area 56 Configuration area 57 MODES OF OPERATION 58 R E P O 58 PROGRAMMABLE AUXILIARY SOCKET POWER SHARE 58 UPS CONFIGURAT...

Страница 7: ...below The UPS is also provided with two dedicated battery packs that allow the easy hot swap replacement of the batteries in full safety thanks to the protected connection system 5000 6000 Nominal po...

Страница 8: ...pansion Power share sockets heat protection Battery expansion connector IEC 10A Power share sockets IN OUT connections box Rear view Cable with terminal Battery pack Manual by pass switch Release slot...

Страница 9: ...Operating on battery power 4 Load powered from bypass 5 Battery back up indicator 6 Load level indicator 7 Configuration area 8 Maintenance action required 9 Timer 10 Measurements display area 11 Stan...

Страница 10: ...the first thing to do is make a check of the contents The pack should contain UPS 2 cable guides Probes for cables terminal board connection Handles kit 3 plastic covers top panels 2 plastic keys to r...

Страница 11: ...ow should be carefully followed BEFORE CARRYING OUT THE FOLLOWING SEQUENCE OF OPERATIONS ENSURE THAT THE UPS IS COMPLETELY SWITCHED OFF AND NOT CONNECTED TO THE ELECTRICITY MAINS OR TO ANY LOAD Once r...

Страница 12: ...ated in the drawing on the side 3 WARNING The display mask is connected to the UPS by a special cable This means that you must extract the mask taking extreme care and avoiding violent jerks or other...

Страница 13: ...load which are added together on the UPS earth conductor The neutral arrangements will only be changed if an isolation transformer is connected or when the UPS is operating with the neutral isolated u...

Страница 14: ...terminal 1 d Connect the phase wire to terminal 2 Output line a Connect the earth wire to terminal 4 b Connect the neutral wire to terminal 5 c Connect the phase wire to terminal 6 6 Ensure that a jum...

Страница 15: ...every 4 seconds 3 If the switch upstream is closed again the UPS must go back to operating from the mains START UP FROM BATTERY 1 Press the general switch located on the front panel 2 Keep the ON but...

Страница 16: ...oltage Fixed The UPS is working on battery power When in this condition the UPS emits a beep at 4 second regular intervals Blinking End of discharge early warning Indicates that the battery s back up...

Страница 17: ...ode A number of examples are shown below SAMPLE GRAPHIC 1 DESCRIPTION Mains voltage Mains frequency UPS output voltage Output voltage frequency Remaining battery backup Battery charge percentage SAMPL...

Страница 18: ...for at least 2 sec The word SET lights and an arrow appears to the left of Frequency The arrow indicates the setting selected To change the selection of the parameter to be modified press the SEL SET...

Страница 19: ...is isolated input is used to switch off the UPS remotely in an emergency Any Remote Emergency Power Off R E P O switch that is normally closed must be connected to the connector located at the back of...

Страница 20: ...ominal output voltage 230V 220V 230V 240V 220 240 in steps of 1V only through the software Operating mode Selects one of the 4 different modes of operation ON LINE ON LINE ECO SMART ACTIVE STAND BY OF...

Страница 21: ...rmitted range for the input frequency for switchover to bypass and for output synchronization 5 0 25 0 5 0 75 1 10 in steps of 1 Bypass voltage thresholds Selects the permitted voltage range for switc...

Страница 22: ...D 4 4 GND 5 GND 6 7 12Vdc interface power supply input 8 Contact closed end of discharge early warning 9 Contact closed battery powered operation Optoisolated contact max 30Vdc 10mA Communication Slo...

Страница 23: ...gram For more detailed information about installation and use see the software user manual in the Manuals folder of the CD ROM supplied To check if a more up to date version of the software is availab...

Страница 24: ...age FAULT C02 WARNING For correct operation of the UPS it is recommended to replace the battery pack only with the UPS switched on 3 The battery packs are connected to the UPS via cables with connecto...

Страница 25: ...he front panel to power the loads STAND BY OFF MODE HAS BEEN SELECTED The mode has to be changed The STAND BY OFF mode back up in fact only powers the loads in the event of a black out THE DISPLAY IS...

Страница 26: ...power can be removed from the load switch the UPS off and then on again if the problem should occur again contact the support service centre THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF...

Страница 27: ...tuck does not open A54 Load threshold set by user A61 Batteries need replacement A62 Battery pack missing or not connected A63 Waiting for batteries to recharge Alarms these problems are more critical...

Страница 28: ...s line the procedure is excluded in case of lockouts due to strong and persistent overloads and lockouts following a short circuit CODE DESCRIPTION L03 Auxiliary power supply incorrect L04 High temper...

Страница 29: ...ing time msec 0 1 BATTERY No batteries V Ah 16 12 7 high rate discharge Recharge time 8 h 4 6 OUTPUT Nominal voltage 7 Vac 220 230 240 1 5 Maximum current A 23 22 21 27 26 25 Static variation 3 1 5 Dy...

Страница 30: ...nominal voltage of 230 Vac battery charging 3 Mains Battery load 0 100 4 Mains battery mains resistive load 0 100 0 5 If the mains frequency is within 5 of the value selected the UPS is synchronized w...

Страница 31: ...70...

Страница 32: ...0MNUM6KNPC...

Отзывы: