59
U
SE
UPS
C
ONFIGURATION
The following table illustrates all the possible configurations that users have at their disposal to best adapt the
UPS to their needs.
LEGEND:
Indicates that the configuration can be modified, both via the configuration
software supplied and also by means of action on the display panel.
Indicates that the configuration can be modified only through the configuration
software supplied.
FUNCTION
DESCRIPTION
PREDEFINED
POSSIBLE CONFIGURATIONS
MODE
Output frequency
Selects the nominal
output frequency
Auto
•
50 Hz
•
60 Hz
•
Auto: automatic self-teaching of the
input frequency
Output voltage
Selects the nominal
output voltage
230V
•
220V
•
230V
•
240V
•
220 ÷ 240 in steps of 1V
(only through the software)
Operating mode
Selects one of the 4
different modes of
operation
ON LINE
•
ON LINE
•
ECO
•
SMART ACTIVE
•
STAND-BY OFF
Switch-on delay
Delay time for
automatic switching
on again after the
mains returns
5 sec.
•
Disabled
•
1 ÷ 255 in steps of 1 sec.
Switch-off due to
minimum load
Automatic UPS
switch-off when in
battery-powered
operation, if the load
is less than 5%
Disabled
•
Enabled
•
Disabled
Back-up
limitation
Maximum battery
operation time
Disabled
•
Disabled (full battery discharge)
•
1 ÷ 65000 in steps of 1 sec.
End of discharge
early warning
Estimated remaining
back-up time for the
end of discharge early
warning
3 min.
1 ÷ 255 in steps of 1 min.
Battery test
Time interval for the
automatic battery test
40 hours
•
Disabled
•
1 ÷ 1000 in steps of 1 hour
=
=