Model 50 Duplex Basket Strainer, Sizes 5

” - 8” 

 

 

Operation

 

The chamber in operation can be determined by observing 
the  position of  the  valve  handle.   The 
handle is on the same side of the center line as 
the chamber in operation (see Figure 4). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Start up

 

Open  both  chamber  vents,  if  strainer  is  so  equipped  (see 
figure  3),  to  expel  air  from  the 
strainer. 

 

Position valve handle in the center to allow both chambers 
to  fill  and  close  the  equalizer  valve,  if  strainer  is  so 
equipped (see figure 2). 

 

Slowly  allow  fluid  to  enter  strainer  by  opening  OUTLET 
valve first, then followed by opening the INLET valve. 

 

CAUTION:   Start  system  GRADUALLY.   This 
eliminates  sudden  shock  to  strainer  and 
other equipment in the line

.

 

 

Close vents when air is expelled and fluid begins to leak out 
vent. 

 

Move  valve  handle  to  extreme  travel  position over one 
clean  basket.    DO  NOT  leave  valve  handle  in  the  center 
position as  both  baskets will become  dirty.      This    would  
require  interrupting flow to clean them. 

 

Seat valve plug lightly by turning valve yoke clockwise.     To 
avoid  excessive  stresses,  stuck  valve  plugs  etc.  when 
operating  at  temperatures  above  120°F  use  only 
minimum  hand  pressure on the valve yoke to position the 
valve plug against the seat. 

 

The  valve  plug  should  be  firmly  seated  during  basket  
cleaning    to    prevent    excessive    leakage  into  the  opened 
chamber. 

Start up, Continued

 

NOTE:  The strainer valve plug is intended to  
divert  flow.   It  is  not  designed to  provide 
absolute tight  shut  off.    Product  design 
criteria  requires valve plug seepage to be low 

enough to provide time for basket cleaning only. 

 

Shut Down

 

Tightly close pipeline valve on  inlet and outlet connections 
of  the  strainer.    Open  vents,  (see 
figure 3), to relieve liquid pressure in the strainer. 

 

 

 

CAUTION:    DO  NOT  loosen  body  covers 
while  there  is  liquid  or  air  flow  from  the 
vent.

 

 

 

 

Switching Flow

 

 

Without Equalizer

 

Turn  lifting  handle  counterclockwise  to  lift  valve  plug  
and  position  turning  handle  (to  extreme travel  position)  
over    clean    basket.    Seat    valve  plug  slightly  by  turning 
lifting handle clockwise. 
 

With Equalizer

 

Open  pressure  equalizer  valve  and  turn  lifting  handle 
counterclockwise to lift valve plug. 
 
Position  turning  handle  (to  extreme  travel  posi-  tion)  over 
clean  basket  and  seat  valve  plug  tightly  by  turning  lifting 
handle clockwise. 
 
Close equalizer valves. 

 

Basket Removal (Yoke Cover)

 

Transfer  flow  from  dirty  to  clean  chamber  (see  Switching 
Flow)  and  open  vents,  and/or  drain  valve  to  relieve  liquid 
pressure in dirty chamber. 
 
When  pressure  is  relieved,  loosen,  but  do  not  remove,  T-
bolt.    Then  drain  fluid  away  through the  chamber  drain 
connection  to  a  level  below  the  basket  seat.      This 
prevents  by-pass  of  dirty fluids. 
 
Swing  yoke  away  from  body  yoke  stud  and  clear  of  body 
cover.  Remove cover. 
 
Remove dirty basket. 