20
7.2
For 6000H(XL)/ 10000H(XL):
Problem
Possible cause
Solution
The #1 Fault LED and
the #6 LED are turned
on, the buzzer beeps
continuously.
The UPS transfers to
fault mode due to internal
overheat.
Make sure the UPS is not overloaded; the air vents are not
blocked and the ambient temperature is not too high. Leave 10
minutes for the UPS to cool down before turning on again. If
failed, please contact the distributor or service center.
The #1 Fault LED and
the #2 and #5 LED are
turned on, and the
buzzer beeps
continuously.
The UPS output is short
circuit.
Remove all the loads. Turn off the UPS. Ensure that the load is
not failed or the UPS has no internal faults before turning it on
again. If failed, please contact the distributor or service center.
The #1 Fault LED and
the #4 LED are turned
on, the UPS beeps
continuously.
The UPS transfers to
fault mode due to its
internal fault.
Please contact the distributor or service center.
The #1 Fault LED and
the #5 LED are turned
on, the UPS beeps
continuously.
The UPS transfers to
fault mode due to its
internal fault.
Please contact the distributor or service center.
The utility power LED
flashes.
The voltage or frequency
of the utility power is out
of the input range of the
UPS.
The UPS is running in battery mode. To save your data and
close the application program. Make sure the utility power is
within the input voltage or frequency range permitted by the
UPS.
The #1 Fault LED and
the #2 LED are turned
on, the UPS beeps
continuously.
The UPS is overloaded
or the load equipment is
faulty.
Check the loads and remove all non-critical equipment.
Recalculate the load power and reduce the number of loads
connected to the UPS. Check that the loads are not failed.
The #1 Fault LED is
turned on, and the
battery LED is flashed,
the buzzer beeps
every second.
The charger of the UPS
is defective.
Please contact the distributor or service center.
Battery LED flashes
Battery low or battery not
connected.
Check the battery. If the battery is damaged, replace the battery
immediately and ensure that the battery breaker is in “ON”
position.
The utility power is
normal, but the UPS
can not turn in Utility
mode
Maintenance switch lost
Please contact the distributor or service center.
Battery not yet been fully
charged.
Keep UPS connected to utility power persistently for more than
10 hours to recharge the batteries again.
UPS overloaded.
Check the loads and remove the non-critical equipment.
Battery discharging
time diminishes
Battery aged.
Replace the batteries. Please contact the distributor to obtain
the parts and replacement service.
The “ON” button is
pressed too briefly.
Press the “ON” button for more than 1 second.
The UPS is not
connected to the battery
or the battery pack
voltage is too low.
Check the battery or recharge the battery.
The UPS cannot
power on after
pressing the ON button
UPS fault.
Please contact the distributor or service center.
Please have the following information at hand before calling the After-Sales Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. Detailed description of the problem.