11
a) Open the terminal block cover located on the rear panel of the UPS.
b) For 6000H(XL) UPS, it is recommended to select the UL1015 10AWG(4mm2) wire
or other insulated wire which complies with AWG Standard for the UPS input and
output wirings. Suggested replacement: Use appropriate cable rated according to
local wiring codes. For 6000H(XL) maximum cable size, please refer to the table in
Page 9.
c) For 10000H(XL), it is recommended to select the UL1015 8AWG(10mm2) wire or
other insulated wire which complies with AWG Standard for the UPS input and
output wirings. Suggested replacement: Use appropriate cable rated according to
local wiring codes. For 10000H(XL) maximum cable size, please refer to the table
in Page 9.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated
current maybe less than the UPS’s maximum input current. Otherwise the receptacle may
be burned and destroyed.
d) Connect the input and output wires to the corresponding input and output terminals
according to the following diagram 1.
e) The protective ground wire refers to the wire connection between the equipment
which consumes electric equipment and the ground wire. The wire diameter of
protective earth ground wire should be at least as above mentioned for each model
and green wire or green wire with yellow ribbon wire is used.
f) After finishing the installation, make sure the wiring is correct.
g) Please install the earth leakage circuit breaker at the output switchboard of the
UPS if necessary.
h) Please turn off all the loads first before connecting them to the UPS, turn on the
loads one by one if the connection is finished.
i) No matter whether the UPS is connected to the mains supply or not, the output of
the UPS may have electricity. Hazardous live parts may exist inside the unit even
the UPS is turned off. To shutdown the output of UPS, power off the UPS, and
disconnect the utility power supply.
j) To ensure adequate battery autonomy, it is recommended to charge the battery for
8 hours before using it. After the connection between the mains supply and the
UPS, set the input breaker to the “ON” position, the UPS will charge the batteries
automatically.
k) If it’s connected to the inductance load such as a monitor or a laser printer to the
UPS, the start-up power should be used for calculating the capacity of the UPS, as
its start-up power consumption is too big.