EasyIO FG32 – Installation Guide v2.0
7
Hardware Configurations
Power supply Connection
Both AC and DC can be used for EasyIO FG Series controller. Refer to electrical specification for the
working range. In order to avoid damage on the controller input/output devices and RS485 connection,
use individual power supply for each controller. If a single power supply is used, make sure controller
power supplies are connected with the same polarity.
Electrical
Power Supply
24V AC +/- 5% or 24V DC +20%/-15%
Consumption
750 mA
Operating Temperature
32 to 150 Deg-F (0 to 65 Deg-C)
Storage Temperature
-4 to 150 Deg-F (-20 to 65 Deg-C)
Operating Humidity
10% to 95% relative humidity non-condensing
Power Supply Connection
Multiple controllers share single transformer connection