EasyIO FD-20i User Reference v1.2

 

 

RS485 Connection 

RS485  connection  must  be terminated  at  both ends  with termination  resistor,  typically  120 Ohms.  It  is 
recommended  to  use  shielded  twisted  pair  wire  (STP)  for  the  wiring.  Lightning  protection  circuit  is 
recommended  to  be  installed  at  one  end  of  the  wiring.  The  controller  should  be  wired  in  daisy  chain 
network topology as shown as image below. If wire branch can be avoided, keep it as short as possible, 
and never connect more than one device to the wire branch.  

Be  careful  if  single  power  supply  is  used  for  all  connected  RS485  device,  make  sure  all  devices  are 
having  the  same  ground  connection.  Make  sure  you  are  connecting  the  same  wire  for  the  same 
terminal position, all “H” terminals connected to the same wire. 

 

 

Daisy Chain Network Topology

 

 

 

RS485 Connection 

 

RS 485 Serial port settings.  

Every EasyIO FC controller comes with 1 physical RS -485 ports respectively.  
However EasyIO provide 2 sets of RS-485 terminals for easy wiring terminations. 
Below is a table showing the default details for serial port.  
 

Port Number 

Protocol Communications supported 

Default Serial port settings 

Remarks 

Port 1 
 

Modbus OR BACnet  
Protocol selection is done via DIP switch 1.  
 
DIP 1 = OFF = Modbus RTU 
DIP 1 = ON = BACnet MSTP 
 

Modbus 

Baud Rate  

: 19.2K 

Parity   

: even 

Data Bit  

: 8 (Not editable) 

Stop Bit  

: 1 

 

BACnet 

Baud Rate 

: 19.2K 

 

-

 

 

 

Содержание FD-20i Series

Страница 1: ...EasyIO FD 20i User Reference v1 2 EasyIO FD 20i Series User Reference...

Страница 2: ...EasyIO FD 20i User Reference v1 2 Document Change Log 1st June 2019 Document created 18th June 2019 Update power supply details 18th March 2020 Updated the temp table selection...

Страница 3: ...IO logo are registered trademarks of EasyIO Holdings Pte Ltd CPT Tool is by Online Tools Inc BACnet and ASHRAE are registered trademarks of American Society of Heating Refrigerating and Air Conditioni...

Страница 4: ...ceiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer o...

Страница 5: ...r Reference v1 2 Contents Introduction 6 Hardware Configurations 7 Power supply Connection 7 RS485 Connection 8 Universal Input Connection 10 Digital Input Connection 10 Buttons and Indications 12 Tec...

Страница 6: ...IO FD 20i Series controller comes with built in bootloader program Built in bootloader program will enable user to upgrade firmware without sending back to factory EasyIO FD20 do not have an Ethernet...

Страница 7: ...se individual power supply for each controller If a single power supply is used make sure controller power supplies are connected with the same polarity Electrical Characteristic Power Supply 24V AC 5...

Страница 8: ...RS485 device make sure all devices are having the same ground connection Make sure you are connecting the same wire for the same terminal position all H terminals connected to the same wire Daisy Chai...

Страница 9: ...The white the spot white square represent the DIP switch toggle button EasyIO FC 20 enlarged DIP switch Setting DIP switch number Functions Remarks 1 Protocol Setting On Bacnet MSTP Off Modus RTU 2 S...

Страница 10: ...0K with Shunt Temperature table selection Temperature table selection is via BACnet objects or Modbus register By default each UI channel temperature table is set to table 1 Table Number Temperature T...

Страница 11: ...nput Terminal Digital Imput Block Channel DI 1 DI 1 DI 2 DI 2 DI 3 DI 3 DI 4 DI 4 DI 5 DI 5 DI 6 DI 6 DI 7 DI 7 DI 8 DI 8 DI 9 DI 9 DI 10 DI 10 UI1 DI 11 UI2 DI 12 UI3 DI 13 UI4 DI 14 UI5 DI 15 UI6 DI...

Страница 12: ...d to indicate the presence of 24VAC power source and internal power 2 ERR ERR is to indicate whenever there is communication errors 3 STS STS is used to indicate the heartbeat of the Microcontroller T...

Отзывы: