background image

 

Automatic Snow/Ice Melting Controller — Installation & Operation Instructions 

sa-1 

3

Roof

2" (50.80mm) min.

SA-1

1" (25.40mm) 

Electrical Junction Box

.5" (12.70mm) Tubing

Gutter

Figure 4a

OPERATION INSTRUCTIONS

The SA-1 snow melting control is designed to energise 

the heating cable only when snow or ice conditions exist 
and there is risk of freezing. If the temperature is below 3°C 
(38°F) and snow is falling, the controller will apply power to 
heating cable. The cable remains energised until 2.75 hours 
after the snow stops. The delay is necessary to ensure the 
heated area dries. If at any time the snow starts falling 
again the controller restarts the heating cycle. 

In spring or fall when the snow conditions are not very 

heavy, the controller may switch on the heated area. For 
this  situation  we  recommend  having  a  manual  switch 
connected in series with the SA-1 to turn it off. 

In wintertime the wind may cover the heated area with 

snow. The SA-1 can not sense this situations and will not 
energise the heating cable. Putting snow on the sensor 
surface can energise the SA-1. 

The SA-1 may be tested for functionality if the outside 

temperature  is  below  25°C  (77°F),  Submerge  the 
temperature  sensor  into  a  glass  with  ice  water  for  5  to 
10 minutes, wet the surface of the moisture sensor, the 
SA-1  should  energise  the  heating  cable.  After  this  test, 
dry off the sensor, disconnect the power for one minute 
and  then  reconnect  it  back.  The  cables  should  remain 
deenergised.

Every year, in the fall the SA-1 must be inspected for 

physical damage and to clean up the snow sensor surface. 
To clean the snow sensor surface: 
1. Disconnect SA-1 from the power supply.
2. With a clean, soft bristle tooth brush clean up the surface 

of the snow sensor.

3. Reconnect SA-1 to the power supply.  

ELECTRICAL SPECIFICATIONS

Functional
Operating temperature 

+3°C (38°F +/-1°F)

Power switch OFF temperature 

+45°C (112°F)

Power switch ON temperature 

+30°C (86°F)

Environmental
Working temperature 

-40°C (-40°F) to 65°C (150°F)

Storage temperature 

-45°C (-49°F) to 70°C (160°F)

Humidity environment 

0 to 100 %

Supply requirements
Power supply voltage 

120VAC 

Frequency 

50/60 Hz

Maximum power consumption 

60W

Output characteristics
Output type 

relay (dry contact)

Contact output 

N.O. max. 16 Amps @ 120VAC

Mounting connector 

.5" (12.70mm) NPT

Power wire length 

3 feet

Figure 4b

 

www.easyheat.com

 

US  T. (800) 537-4732 / F. (888) 324-2440
CAN  T. (800) 794-3766 / F. (800) 361-4574