background image

1.  Mount the SA-1 securely in upright position in an 

open space, in direct contact with snowfall pattern 
with  a  .5"  (12.70mm)  NPT  mounting  connector. 
The unit is water-resistant, but it is not designed 
to  be  submerged  or  immersed  in  water.  Ensure 
that  the  mounting  location  is  close,  less  than 
2.5  ft  (76.20cm)  to  the  electrical  junction  box.  
See Fig. 4a &4b.

 

2.  The SA-1 can be connected to the building power 

supply as per Fig. 2 or Fig. 3. Before connecting the 
controller  to  the  electrical  power  supply,  consult 
the local, state or provincial, and national electrical 
code.  The  electrical  code  may  require  a  Ground 
Fault Protection device to be used. 

3.  Ensure  that  all  pipe  connections  are  sealed  to 

prevent any penetration of water inside of conduit 
or electrical junction box.

2     sa-1   

Automatic Snow/Ice Melting Controller — Installation & Operation Instructions

SA - 1

AWG #12 RED/YELLOW

AWG #12 RED/YELLOW

AWG #18 BLACK

AWG #18 WHITE

OPTIONAL MANUAL SWITCH OR TIMER

SNOW MELTING
CABLE

OPTIONAL
ON/OFF
SWITCH

INSTALLATION FOR DIRECT CONTROL OF LOAD

* ELECTRICAL CODE MAY REQUIRE USE OF A GROUND FAULT PROTECTION DEVICE.

Figure 2 — Installation for Direct Control of Load

*Electrical code may require use of a ground fault protection device.

SA - 1

AWG #12 RED/YELLOW

AWG #12 RED/YELLOW

AWG #18 BLACK

AWG #18 WHITE

OPTIONAL
ON/OFF
SWITCH

COIL

120

VAC

OPTIONAL MANUAL SWITCH OR TIMER

SNOW MELTING
CABLE

INSTALLATION FOR CONTACTOR CONTROLLED LOAD (240 VAC)

* ELECTRICAL CODE MAY REQUIRE USE OF A GROUND FAULT PROTECTION DEVICE.

Figure 3 — 
Installation for Contactor Controlled Load

*Electrical code may require use of a ground fault protection device.

  

www.easyheat.com

 

US  T. (800) 537-4732 / F. (888) 324-2440
CAN  T. (800) 794-3766 / F. (800) 361-4574