16
GAS
SUPPLY
PIPING
1. All gas piping and connections shall be made in accordance with all applicable
local codes and the latest versions of CAN/CGA B-149 or ANSI standard Z223.1.
2. Connect the burner to gas supply with flexible gas connector.
3. A drip leg must be installed in the gas line at the heater inlet connection tee
followed by a pipe drop to the heater. Failure to provide a drip leg could result in
condensation and foreign matter passing into the gas valve. Failure to install a
drip leg in the gas line can cause property damage, injury or death and will void
the heater warranty.