Register Order
controls the order in which the Eastron Digital meter receives or sends
floating-point numbers: - normal or reversed register order. In normal mode, the two registers
that make up a floating point number are sent most significant register first. In reversed
register mode, the two registers that make up a floating point number are sent least significant
register first. To set the mode, write the value '2141.0' into this register - the instrument will
detect the order used to send this value and set that order for all Modbus Protocol transactions
involving floating point numbers.
It is perfectly feasible to change Eastron Digital meter set-up using a general purpose Modbus
Protocol master, but often easier to use the Eastron Digital meter display or Eastron Digital
meter configurator software, especially for gaining password protected access. The Eastron
Digital meter configurator software has facilities to store configurations to disk for later retrieval
and rapid set up of similarly configured products.
Password
Length : 4 byte
Data Format : Float
40029
15
Network
Baud Rate
00
1C
Write the network port baud rate
for MODBUS Protocol, where:
0 = 2400 baud. 1 = 4800 baud.
2 = 9600 baud, default.
3 = 19200 baud. 4 = 38400 baud.
Length : 4 byte
Data Format : Float
r/w
40087
44
Pulse 1
Energy
Type
00
56
Write MODBUS Protocol
input parameter for pulse
output 1:
1: import active energy
2: total active energy
4: export active energy, default
5: import
re
active energy
6: total
re
active energy
8: export
re
active energy
Length : 4 byte
Data Format : Float
r/w
461457
30729
Reset
F0
10
00 00: reset the Maximum demand
Length: 2 byte
Data Format: Hex
wo
464513
464513
Serial
number
FC
00
Serial number
Length: 4 byte
Data Format: unsigned int32
Note: Only read
ro
B+G e-tech GmbH °
DE 01979 Lauchhammer °
www.eastron-germany.de