Data Format : Float
40013
7
Pulse1
Width
00
OC
Write pulse1 on period in
milliseconds: 60, 100 or 200,
default 100.
Length : 4 byte
Data Format : Float
r/w
40015
8
Password
Lock
00
OE
Write any value to password lock
protected registers.
Read password lock status:
0 = locked. 1 = unlocked.
Reading will also reset the
password timeout back to one
minute.
Length : 4 byte
Data Format : Float
r
40019
10
Network
Parity Stop
00
12
Write the network port parity/stop
bits for MODBUS Protocol, where:
0 = One stop bit and no parity,
default. 1 = One stop bit and even
parity. 2 = One stop bit and odd
parity.3 = Two stop bits and no
parity.Requires a restart to become
effective.
Length : 4 byte
Data Format : Float
r/w
40021
11
Network
Node
00
14
Write the network port node
address: 1 to 247 for MODBUS
Protocol, default 1. Requires a
restart to become effective.
Length : 4 byte
Data Format : Float
r/w
40023
12
Pulse1
Divisor1
00
16
Write pulse divisor index: n
= 0 to 5
0--0.0025 kWh(kVArh)/imp
1--0.01 kWh(kVArh)/imp
2--0.1 kWh(kVArh)/imp
3
—1 kWh(kVArh)/imp
4-10 kWh(kVArh)/imp
5-100 kWh(kVArh)/imp
Length : 4 byte
Data Format : Float
r/w
40025
13
Password
00
18
Write password for access to
protected registers.
r/w