User Manual 200 kVA-1200 kVA UPS
Appendix 1 Alarm List
90
608
Bypass under-frequency
1.
Check whether the bypass voltage sampling is
normal
617
Reverse bypass phase sequence
1.
Check whether the bypass voltage for inverted
sequence
2.
Check whether the bypass voltage sampling line is
reversed
600/601/602
Effective value overvoltage of
bypass (A B C)
Abnormal bypass input or abnormal sampling
603/604/605
Effective value under-voltage of
bypass (A B C)
Abnormal bypass input or abnormal sampling
607
Bypass over-frequency
Abnormal bypass input or abnormal sampling
608
Bypass under-frequency
Abnormal bypass input or abnormal sampling
614/615/616
Bypass phase loss
Abnormal bypass input or abnormal sampling
655
Bypass overload alarm
Bypass overload or abnormal sampling
628
Bypass overload 135%
Bypass overload or abnormal sampling
629
Bypass overload 150%
Bypass overload or abnormal sampling
656/657/658
ECO over-voltage (A B C)
Bypass beyond upper and lower limit of ECO
659/660/661
ECO under-voltage (A B C)
Bypass beyond upper and lower limit of ECO
662
ECO frequency over-voltage
Bypass beyond upper and lower limit of ECO
663
ECO frequency under-voltage
Bypass beyond upper and lower limit of ECO
648
Quick over-voltage of bypass
Abnormal bypass or RCD load overload
639
Quick power failure of bypass
Load impact, or quick power failure
651
Quick under-voltage of bypass
Load impact, or quick power failure
700/701/702
Effective value overvoltage of output
(A B C)
Abnormal inverter output or abnormal sampling
703/704/705
Effective value undervoltage of
bypass (A B C)
Abnormal inverter output or abnormal sampling
718
Output over-frequency
Abnormal inverter output
719
Output under-frequency
Abnormal inverter output
1108
Output overload alarm
Output overload or abnormal sampling
1060
Total output overload 105% alarm of
inverter
Output overload or abnormal sampling
1061
Total output overload 110% alarm of
inverter
Output overload or abnormal sampling
1062
Total output overload 125% alarm of
inverter
Output overload or abnormal sampling
1063
Total output overload 150% alarm of
inverter
Output overload or abnormal sampling
720
Quick power failure of (inverter)
output
Load impact, or quick power failure
712
Quick over-voltage of (inverter)
output
Abnormal output