User Manual 200 kVA-1200 kVA UPS
7 Troubleshooting
80
7 Troubleshooting
Please refer to Table 7-1 for the common failure removal method.
Table 7-1 Common failure and removal method
Problems
Possible cause
Solution
Rectifier failure
Input AC voltage beyond standard
Confirm whether the input distribution voltage is
abnormal
Abnormal phase sequence of
three-phase input of UPS
Check whether phase sequence of three-phase input
of UPS is correct
Wave-based current limit and
over-current failure of rectifier
Check the failure record list in the display panel to
see if there is any failure. If yes, access the control
interface to clear the failure
Frequent switching between the
mains and the battery
Access the control interface to clear the failure
Power unit failed
Replace the power unit
Inverter failure, and
UPS switching to
bypass power supply
Output overload or short circuit
protection
Reduce the load, or remove the short circuit of the
load
Overheat protection of UPS
Install the air conditioner or ventilation facilities for
the machine room to ensure the normal temperature
of the machine room
Wave-based current limit and
over-current failure of inverter
Check the failure record list in the display panel to
see if there is any failure. If yes, access the control
interface to clear the failure
Power unit failed
Replace the power unit
AC system failing to
switch to battery
mode
Wave-based current limit and
over-current failure of charger
Check the failure record list in the display panel to
see if there is any failure. If yes, access the control
interface to clear the failure
Improper battery connection
Check whether the battery is connected reversely or
not connected
Battery undervoltage
Check the battery for any quality problems
Power unit failed
Replace the power unit
Bypass failure
Abnormal bypass frequency
Check whether the bypass input frequency is
abnormal
Abnormal bypass voltage
Check whether the bypass input voltage is abnormal
Short circuit or open circuit of
bypass SCR
Check bypass SCR and insurance for short circuit or
open circuit
Note:
For the replacement and maintenance of the components specified in Chapter 7 Troubleshooting and Appendix 2
Alarm List, please consult the maintenance engineer.