6. TEST RUNNING

Operate according to "gist for test running" on the electric control box 

cover.

Test running can not start until the outdoor unit has been 

connected to the power for 12hr. 

Test running can not start until all the valves are affirmed 

open.

Never make the forced running. (Or the protector sits back, 

danger will occur.)

CAUTION

7. PRECAUTIONS ON REFRIGERANT

LEAKAGE

This air conditioner(A/C) adopts inncouous and nonflammable 

refrigerant. The locating room of the A/C should big engough 

that any refrigerant leakage is unable to reach critical thickness.

So certain esssential action can be taken on time.

A[kg]
B[m ]

3

Critical thickness------the Max. thickness of Freon without any 

harm to person.
Refrigerant critical thickness: 0.44[kg/m ] for R410A. 

Confirm the critical thickness through follow steps, and take 

necessary actions. 
1. Calculate  the  sum  of  the  charge volume  (A[kg]) Total

Refrigerant volume of 10HP=factory refrigerant

superaddition

2. Calculate  the  indoor  cubage  (B[m ]) (as  the  minimum

cubage.

3

3. Calculate the refrigerant thickness

critical thickness

Counter measure against over high thickness

1. Installmechanicalventilator to reduce the refrigerant thickness

under critical level. (ventilate regularly)

  

2. Install leak alarm facility related to mechanical ventilator if

you can not regularly ventilate.

b. Leak alarm related to mechanical ventilator

A. Ventilation 

    peristome 

(Leak hunting siren should be installed in 

places easily keep refrigerant) 

Indoor unit

Outdoor unit

Indoor unit

Room full of leak refrigerant

(All refrigerant has run up)

14

8. TURN OVER TO CUSTOMER

The owner's manual of indoor unit and owner's manual of

outdoor or unit must be turned over to the customer. Explain

the contents in the owner’s manual to the customers in details.

Please press “constraint cool” button to carry out refrigerant 

recycling process. Keep the low pressure above 0.2MPa, other 

wise compressor may be burnt out.  

Fig. 7-1

NOTE

  1

ON 

Obtain network address automatically

OFF  Obtain network address manually

 

  2 

ON 

Revocation indoor unit network address

 

OFF 

/

SW3

SW-1

Table 5-3

7.1  Important information for the used 

       refrigerant

This product has the fluorinated gas, it is forbidden to release to air. 

Refrigerant type: R410A; Volume of GWP: 2088;

GWP=Global Warming Potential

Attention:

Frequency of Refrigerant Leak Checks

1) For equipment that contains fluorinated greenhouse gases in

quantities of 5 tonnes of CO

2

 equivalent or more,but of less than

50 tonnes of CO

2

 equipment,at least every 12 months, or where

a leakage detection system is installed, at least every 24 months.

2) For equipment that contains fluorinated greenhouse gases in

quantities of 50 tonnes of CO

2

 equivalent or more,but of less than

500 tonnes of CO

2

 equipment,at least every six months, or where

a leakage detection system is installed, at least every 12 months.

3) For equipment that contains fluorinated greenhouse gases in

quantities of 500 tonnes of CO

2

 equivalent or more,at least every

three months, or where a leakage detection system is installed,

at least every six months.

4) Non-hermetically sealed equipment charged with fluorinated

greenhouse gases shall only be sold to the end user where evidence

is provide that the installation is to be carried out by an undertaking

certified person.

5) Only certificated person is allowed to do installation, operation

and maintenance.

    

Model

Refrigerant/kg

tonnes CO

2

 equivalent

2.95
2.95
3.30
3.90
3.90
4.50

6.16 
6.16 
6.89 
8.14 
8.14
9.40 

12kW
14kW
16kW
18kW

8kW

10.5kW

Factory charge

V.2

Содержание EVRO-120NDC

Страница 1: ...MANUAL DE INSTALACI N Y MANUAL DE USUARIO MODELOS EVRO 120NDC EVRO 140NDC EVRO 160NDC EVRO 160RDC VRV V 2...

Страница 2: ...NDICE Manual de instalaci n 3 Manual de usuario 15 V 2...

Страница 3: ...er trabajo el ctrico Aseg rese de que todos los interruptores est n desconectados El no hacerlo puede causar una descarga el ctrica Conecte el cable de conexi n correctamente Si el cable de conexi n s...

Страница 4: ...Para la purga de aire utilizar una bomba de vac o No utilice refrigerante cargado en la unidad exterior para purgar el aire El refrigerante de purga no est contenido en la unidad Cableado el ctrico A...

Страница 5: ...laci n y mantenimiento No lo instale en un lugar que tenga una elevada exigencia de silencio como una habitaci n El aislamiento de las partes met licas del edificio y el aire acondicionado debe cumpli...

Страница 6: ...a en la figura siguiente Salida de agua Salida de conexiones Salida de agua reservada PRECAUCI N INSTALACI N DE LAS TUBER AS FRIGOR FICAS PRECAUCI N Compruebe que la diferencia de altura entre la unid...

Страница 7: ...buidor intermedio y del distribuidor final Distribuidores frigor ficos intermedios y finales Di metros de tuber a seg n la capacidad Consulte la Tabla jemplo En la F la capacidad total aguas abajo de...

Страница 8: ...ser m s de 8 0kW Cuando la capacidad de las unidades interiores sea mayor que la capacidad nominal de la unidad exterior 100 se atenuar la capacidad de las unidades interiores Cuando la capacidad de l...

Страница 9: ...ermitido Tuber a T a Primer m todo de conex Segundo m todo de conexi n Segundo m todo de conexi n Primer m todo de conexi n Long equivalente Longitud total Dist ncia m xima L Longitud total Longitud e...

Страница 10: ...y baja presi n de la unidad exterior deber n estar cerradas cuando realice la presurizaci n con nitr geno La prueba de estanquidad nunca debe realizarse con ox geno gases inflamables o gas venenoso Us...

Страница 11: ...empalmes Cableado de comunicaci n exterior interior Alimentaci n Ud Ext Ud Exterior Control centralizado Cableado de comunicaci n exterior interior Cableado de comunicaci n exterior interior Usar cabl...

Страница 12: ...l cable de comunicaci n entre la unidad interior y la unidad exterior junto con las tuber as de refrigerante La instalaci n debe cumplir con la norma el ctrica local El tama o del cable debe cumplir l...

Страница 13: ...e deben configurar las direcciones de las unidades interiores nunca repetir direcciones PRECAUCI N El cable de comunicaci n de la unidad interior exterior es un circuito de baja tensi n 2 5Vdc entre P...

Страница 14: ...s equipos debe ser lo suficientemente grande para que en caso de una fuga de refrigerante no se alcance la densidad de fre n cr tica Adem s de esto usted puede tomar algunas medidas previas Calcular l...

Страница 15: ...MACI N IMPORTANTE DE SEGURIDAD 15 NOMBRE DE LAS PARTES 16 LIMITES DE OPERACI N 17 FUNCIONAMIENTO Y RENDIMIENTO 17 C DIGOS DE ERROR UD EXTERIOR 18 PROBLEMAS QUE NO SON DEL EQUIPO 20 PROBLEMAS Y CAUSAS...

Страница 16: ...nuevo para desactivar el modo de refrigeraci n forzada Comprobaci n de par metros SW2 Refrigeraci n forzada 1 Secuencia de par metros que se muestran a cada pulsaci n del pulsador SW2 Equipos de 12 14...

Страница 17: ...ueada Hay un exceso de polvo y basura adherida al filtro de polvo en la unidad interior La salida de aire de la unidad interior est estrangula Cuando se activan los elementos de protecci n el indicado...

Страница 18: ...exterior Error de las sondas T3 tuber a y o T4 ambiente Protecci n de voltaje Error del motor ventilador DC El valor de la sonda T3 es superior a 27 C durante 5 min en modo calefacci n Error E6 ha ap...

Страница 19: ...ta temperatura de condensaci n Protecci n por alta temperatura de evaporaci n Error de comunicaci n entre unidad exterior e interiores Error de m dulo inverter Protecci n de bajo voltaje DC Protecci n...

Страница 20: ...normal que se escuche este ruido Un sonido chirriante pishi pishi se escucha cuando el sistema se detiene despu s de funcionar en calefacci n La expansi n y contracci n de las piezas de pl stico caus...

Страница 21: ...est bloqueado Los intercambiadores de calor de la unidad interior e exterior est n sucios El filtro de aire est sucio La entrada salida de las unidades interiores exteriores est bloquea Puertas y vent...

Страница 22: ...ocidad del ventilador solo puede configurarse en los modos refrigeraci n calefacci n y ventilaci n Cuando se selecciona el modo autom tico la unidad interior cambiar autom ticamente la velocidad del v...

Страница 23: ...8 SERVICIO POST VENTA Para consular su servicio t cnico m s cercano acceda a la p gina web www easelectric es V 2...

Страница 24: ...INSTALLATION S AND OWNER S MANUAL MODELS EVRO 120NDC EVRO 140NDC EVRO 160NDC EVRO 160RDC VRV V 2...

Страница 25: ...Table of contents Installation s Manual 3 Owner s Manual 28 V 2...

Страница 26: ...n all pole disconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring accordi...

Страница 27: ...ith 1 0 mm or more thickness for 15 9 Use copper pipe with 1 0 mm or more thickness for 19 0 Flare nut and flare works are also different form those of the conventional refrigerant take out the flare...

Страница 28: ...al parts of the building and the air conditioner should comply with the regulation of National Electric Standard Install indoor unit outdoor unit power cord and connecting wire at least 1m away from T...

Страница 29: ...e installing the outdoor unit pay attention to the installation place and the drainage pattern if it s installed at the alpine zone the frozen condensed water will block up the water outlet please pul...

Страница 30: ...ipe EVRI BP1 EVRI BP1 19 1 R410A Indoor unit connecting pipes diameters 1 R410A Indoor unit connecting pipes diameters 4 3 2 Example 1 In the Fig 4 5 The downstream inner units of the L2 and its total...

Страница 31: ...ater than or equal to the sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time When the capacity of indoor unit is greater than or equal t...

Страница 32: ...and its total capacity is 28 2 56 the size of pipe L2 is 15 9 9 5 and the branch pipe B should be EVRI BP1 The downstream inner units of the main pipe L4 are N3 N4 and its total capacity is 28 2 56 th...

Страница 33: ...ing vacuum pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant according to the di...

Страница 34: ...ndoor unit Indoor unit Signal wire between indoor units N L P Q E L N E Q P E Y X L N E L N E Q P Q P Y E X Branch Box Branch Box CCM E Y X E Y X Branch Box Please use 3 core shielded wire and connect...

Страница 35: ...unication Bus Indoor Unit Indoor Unit wire distribution box Switch Circuit breaker Switch Circuit breaker Power wiring outdoor Central control monitor CCM CCM Computer in broken line table users can p...

Страница 36: ...s of indoor units NOTE Single phase indoor unit Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken lin...

Страница 37: ...t must be turned over to the customer Explain the contents in the owner s manual to the customers in details Please press constraint cool button to carry out refrigerant recycling process Keep the low...

Страница 38: ...j and indoor 27 19 dry wet bulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25...

Страница 39: ...3 560 7 948 5 838 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 40: ...lb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 12 3 kW Seasonal space coolin...

Страница 41: ...3 560 7 948 5 838 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 42: ...bulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 14 kW Seasonal space coolin...

Страница 43: ...3 654 8 067 6 436 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 44: ...bulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 14 kW Seasonal space coolin...

Страница 45: ...3 654 8 067 6 436 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 46: ...ulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 15 5 kW Seasonal space cooli...

Страница 47: ...4 791 10 407 7 816 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and o...

Страница 48: ...ulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 15 5 kW Seasonal space cooli...

Страница 49: ...4 4 791 10 407 7 816 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and...

Страница 50: ...eclared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 17 5 kW Seasonal space cooling en...

Страница 51: ...97 10 238 8 407 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and outdo...

Страница 52: ...r inlet air outlet Fig 1 All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall p...

Страница 53: ...he appliance shall be installed in accordance with national wiring regulations Do not use the air conditioner for other purposes In order to avoid any quality deterioration do not use the unit for coo...

Страница 54: ...e sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time The outdoor unit window shades should be periodic cleaning in case of being jammed...

Страница 55: ...E 4 2 About power cut If power is cut during operation stop all the operation immediately Power comes again The lamp on the display panel of indoor unit flashes And then unit will auto restart Mishand...

Страница 56: ...displayed in the Control Panel Those Indoor Units which are running on Heating Mode will run continuously If the Air Conditioner Administrator has set running mode then the air conditioner can not ru...

Страница 57: ...n between the real and the setting speed Typhoon protection Indoor evaporator hi tempprotection Low pressure protection Hi pressure protection Inverter module protection Compressor discharge protectio...

Страница 58: ...ound is heard when the system is in cooling operation or at a stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system s...

Страница 59: ...or unit and indoor unit heat exchanger is dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Sunlight directly shine Too much heat resource Outdoo...

Страница 60: ...pressed Check whether the signal transmitter of the remote controller is properly directed to the infrared signal receiver of the indoor unit when the ON OFF button is pressed Directly transmit the s...

Страница 61: ...V 2 www easelectric es...

Отзывы: