EAS Electric EVRO-120NDC Скачать руководство пользователя страница 30

7

NOTE

Size of main pipe and corresponding branch joint and branch 

header

Table 4-2

Select refrigerant pipe

Fig. 4-3

The unit body

Affiliated heat pump belt

Site pipe side

Cut from upward

4.3  Heat Insulation

Do the heat insulation to the pipes of air side and liquid side 

separately. The temperature of the pipes of air side and liquid side 

when cooling, for avoiding condensation please do the heat 

insulation fully.

     The air side pipe should use closed cell foamed insulation 

material, which the fire-retardant is B1 grade and the heat 

resistance over 120°C.

      When the external diameter of copper pipe≤Φ12.7mm, the 

thickness of the insulating layer at least more than 15mm; 

  When the external diameter of copper pipe≥Φ15.9mm, the 

thickness of the insulating layer at least more than 20mm.

     Please use attached heat-insulating materials do the heat 

insulation without clearance for the connecting parts of the indoor 

unit pipes.

Fig. 4-2

Check point of outdoor unit

Check point of indoor unit

D

B

A

C

Pipe definition

Pipe connect position

The pipe between outdoor unit to the 

first branch of indoor unit.

The main pipes of 

indoor unit

Code

Indoor unit branch

pipes components

L2~L5

L1

a,b,c,
d,e,f

A,B,C,
D,E

The first connect methond

a

b

c

e

f

d

L

1

L

2

L

3

L

4

L

5

A

B

C

D

E

NOTE

4.4 Confirmation for the diameters of indoor 

       unit connecting pipes

A<166

166≤A<230

Total capactiy of

the downstream

inner units

Main pipe size

mm

Iiquid pipe

Φ15.9

Φ9.5

Φ9.5

Branch Pipe

EVRI-BP1

EVRI-BP1

Φ19.1

R410A Indoor unit connecting pipes diameters 

1) R410A Indoor unit connecting pipes diameters 4-3

2) Example 1

In the Fig.4-5,The downstream inner units of the

L2,and its total capacity is 28×2

56

refers to the Table 4.4,the

air/liquid side of L2 is

Φ15.9/Φ9.5

N

1

(28)

N

3

(28)

N

5

(28)

N

6

(22)

N

2

(28)

N

4

(28)

A

B

D

E

C

a

b

c

e

f

d

L

1

L

2

L

5

L

3

L

4

The straight distance between copper pipe turning and the contig-

uous branch pipe is at least 0.5m;

air side

 (mm)

liquid si-

de

(mm)

A<160

160≤A<230

Φ15.9

Φ9.5

Φ19.1

Φ9.5

EVRI-BP1

EVRI-BP1

EVRI-BP1

EVRI-BP2

Φ19.1

Φ9.5

Φ22.2

Φ9.5

Main pipe size when the tot-

al equivalent piping length 

of air side is <90m

4.4   Connecting method

Main pipe

The branch pipes 

of indoor unit

The pipe after the first branch do not 

drect connect with the indoor unit.

The pipe after the branch connect with

the indoor unit.

The pipes connect with the main pipe

the branch pipe and the the main pipe

of indoor unit.

The First Line Branch Pipe

Outdoor Unit

The First Line Branch Pipe

Outdoor Unit(Take Model 160 for example)

The second connect methond

Intdoor Units

Fig. 4-4

Fig. 4-5

The distance between the first buranch to the last indoor unit is 

more than 15m,choose the second connect methond.

The pipe between the indoor unit to the closest branch must less

 than 15m.

Table 4-3

Air pipe

R410A outdoor unit connecting pipes diameters 

Total capa-

ctiy of The

outdoor 

units

Table 4-4

Main pipe size when the tot-

al equivalent piping length 

of air side is ≥90m

air side

 (mm)

liquid si-

de

(mm)

The first Line

 Branch Pipe

The first Line

 Branch Pipe

4.5 Confirmation for the diameters of outdoor 

       unit connecting pipes

V.2

Содержание EVRO-120NDC

Страница 1: ...MANUAL DE INSTALACI N Y MANUAL DE USUARIO MODELOS EVRO 120NDC EVRO 140NDC EVRO 160NDC EVRO 160RDC VRV V 2...

Страница 2: ...NDICE Manual de instalaci n 3 Manual de usuario 15 V 2...

Страница 3: ...er trabajo el ctrico Aseg rese de que todos los interruptores est n desconectados El no hacerlo puede causar una descarga el ctrica Conecte el cable de conexi n correctamente Si el cable de conexi n s...

Страница 4: ...Para la purga de aire utilizar una bomba de vac o No utilice refrigerante cargado en la unidad exterior para purgar el aire El refrigerante de purga no est contenido en la unidad Cableado el ctrico A...

Страница 5: ...laci n y mantenimiento No lo instale en un lugar que tenga una elevada exigencia de silencio como una habitaci n El aislamiento de las partes met licas del edificio y el aire acondicionado debe cumpli...

Страница 6: ...a en la figura siguiente Salida de agua Salida de conexiones Salida de agua reservada PRECAUCI N INSTALACI N DE LAS TUBER AS FRIGOR FICAS PRECAUCI N Compruebe que la diferencia de altura entre la unid...

Страница 7: ...buidor intermedio y del distribuidor final Distribuidores frigor ficos intermedios y finales Di metros de tuber a seg n la capacidad Consulte la Tabla jemplo En la F la capacidad total aguas abajo de...

Страница 8: ...ser m s de 8 0kW Cuando la capacidad de las unidades interiores sea mayor que la capacidad nominal de la unidad exterior 100 se atenuar la capacidad de las unidades interiores Cuando la capacidad de l...

Страница 9: ...ermitido Tuber a T a Primer m todo de conex Segundo m todo de conexi n Segundo m todo de conexi n Primer m todo de conexi n Long equivalente Longitud total Dist ncia m xima L Longitud total Longitud e...

Страница 10: ...y baja presi n de la unidad exterior deber n estar cerradas cuando realice la presurizaci n con nitr geno La prueba de estanquidad nunca debe realizarse con ox geno gases inflamables o gas venenoso Us...

Страница 11: ...empalmes Cableado de comunicaci n exterior interior Alimentaci n Ud Ext Ud Exterior Control centralizado Cableado de comunicaci n exterior interior Cableado de comunicaci n exterior interior Usar cabl...

Страница 12: ...l cable de comunicaci n entre la unidad interior y la unidad exterior junto con las tuber as de refrigerante La instalaci n debe cumplir con la norma el ctrica local El tama o del cable debe cumplir l...

Страница 13: ...e deben configurar las direcciones de las unidades interiores nunca repetir direcciones PRECAUCI N El cable de comunicaci n de la unidad interior exterior es un circuito de baja tensi n 2 5Vdc entre P...

Страница 14: ...s equipos debe ser lo suficientemente grande para que en caso de una fuga de refrigerante no se alcance la densidad de fre n cr tica Adem s de esto usted puede tomar algunas medidas previas Calcular l...

Страница 15: ...MACI N IMPORTANTE DE SEGURIDAD 15 NOMBRE DE LAS PARTES 16 LIMITES DE OPERACI N 17 FUNCIONAMIENTO Y RENDIMIENTO 17 C DIGOS DE ERROR UD EXTERIOR 18 PROBLEMAS QUE NO SON DEL EQUIPO 20 PROBLEMAS Y CAUSAS...

Страница 16: ...nuevo para desactivar el modo de refrigeraci n forzada Comprobaci n de par metros SW2 Refrigeraci n forzada 1 Secuencia de par metros que se muestran a cada pulsaci n del pulsador SW2 Equipos de 12 14...

Страница 17: ...ueada Hay un exceso de polvo y basura adherida al filtro de polvo en la unidad interior La salida de aire de la unidad interior est estrangula Cuando se activan los elementos de protecci n el indicado...

Страница 18: ...exterior Error de las sondas T3 tuber a y o T4 ambiente Protecci n de voltaje Error del motor ventilador DC El valor de la sonda T3 es superior a 27 C durante 5 min en modo calefacci n Error E6 ha ap...

Страница 19: ...ta temperatura de condensaci n Protecci n por alta temperatura de evaporaci n Error de comunicaci n entre unidad exterior e interiores Error de m dulo inverter Protecci n de bajo voltaje DC Protecci n...

Страница 20: ...normal que se escuche este ruido Un sonido chirriante pishi pishi se escucha cuando el sistema se detiene despu s de funcionar en calefacci n La expansi n y contracci n de las piezas de pl stico caus...

Страница 21: ...est bloqueado Los intercambiadores de calor de la unidad interior e exterior est n sucios El filtro de aire est sucio La entrada salida de las unidades interiores exteriores est bloquea Puertas y vent...

Страница 22: ...ocidad del ventilador solo puede configurarse en los modos refrigeraci n calefacci n y ventilaci n Cuando se selecciona el modo autom tico la unidad interior cambiar autom ticamente la velocidad del v...

Страница 23: ...8 SERVICIO POST VENTA Para consular su servicio t cnico m s cercano acceda a la p gina web www easelectric es V 2...

Страница 24: ...INSTALLATION S AND OWNER S MANUAL MODELS EVRO 120NDC EVRO 140NDC EVRO 160NDC EVRO 160RDC VRV V 2...

Страница 25: ...Table of contents Installation s Manual 3 Owner s Manual 28 V 2...

Страница 26: ...n all pole disconnection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring accordi...

Страница 27: ...ith 1 0 mm or more thickness for 15 9 Use copper pipe with 1 0 mm or more thickness for 19 0 Flare nut and flare works are also different form those of the conventional refrigerant take out the flare...

Страница 28: ...al parts of the building and the air conditioner should comply with the regulation of National Electric Standard Install indoor unit outdoor unit power cord and connecting wire at least 1m away from T...

Страница 29: ...e installing the outdoor unit pay attention to the installation place and the drainage pattern if it s installed at the alpine zone the frozen condensed water will block up the water outlet please pul...

Страница 30: ...ipe EVRI BP1 EVRI BP1 19 1 R410A Indoor unit connecting pipes diameters 1 R410A Indoor unit connecting pipes diameters 4 3 2 Example 1 In the Fig 4 5 The downstream inner units of the L2 and its total...

Страница 31: ...ater than or equal to the sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time When the capacity of indoor unit is greater than or equal t...

Страница 32: ...and its total capacity is 28 2 56 the size of pipe L2 is 15 9 9 5 and the branch pipe B should be EVRI BP1 The downstream inner units of the main pipe L4 are N3 N4 and its total capacity is 28 2 56 th...

Страница 33: ...ing vacuum pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant according to the di...

Страница 34: ...ndoor unit Indoor unit Signal wire between indoor units N L P Q E L N E Q P E Y X L N E L N E Q P Q P Y E X Branch Box Branch Box CCM E Y X E Y X Branch Box Please use 3 core shielded wire and connect...

Страница 35: ...unication Bus Indoor Unit Indoor Unit wire distribution box Switch Circuit breaker Switch Circuit breaker Power wiring outdoor Central control monitor CCM CCM Computer in broken line table users can p...

Страница 36: ...s of indoor units NOTE Single phase indoor unit Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken lin...

Страница 37: ...t must be turned over to the customer Explain the contents in the owner s manual to the customers in details Please press constraint cool button to carry out refrigerant recycling process Keep the low...

Страница 38: ...j and indoor 27 19 dry wet bulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25...

Страница 39: ...3 560 7 948 5 838 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 40: ...lb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 12 3 kW Seasonal space coolin...

Страница 41: ...3 560 7 948 5 838 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 42: ...bulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 14 kW Seasonal space coolin...

Страница 43: ...3 654 8 067 6 436 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 44: ...bulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 14 kW Seasonal space coolin...

Страница 45: ...3 654 8 067 6 436 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and ou...

Страница 46: ...ulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 15 5 kW Seasonal space cooli...

Страница 47: ...4 791 10 407 7 816 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and o...

Страница 48: ...ulb Declared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 15 5 kW Seasonal space cooli...

Страница 49: ...4 4 791 10 407 7 816 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and...

Страница 50: ...eclared energy efficiency ratio or gas utilisation efficiency auxiliary energy factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 17 5 kW Seasonal space cooling en...

Страница 51: ...97 10 238 8 407 7 kW kW kW kW kW kW Item Symbol Value Unit Item Rated heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and outdo...

Страница 52: ...r inlet air outlet Fig 1 All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall p...

Страница 53: ...he appliance shall be installed in accordance with national wiring regulations Do not use the air conditioner for other purposes In order to avoid any quality deterioration do not use the unit for coo...

Страница 54: ...e sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time The outdoor unit window shades should be periodic cleaning in case of being jammed...

Страница 55: ...E 4 2 About power cut If power is cut during operation stop all the operation immediately Power comes again The lamp on the display panel of indoor unit flashes And then unit will auto restart Mishand...

Страница 56: ...displayed in the Control Panel Those Indoor Units which are running on Heating Mode will run continuously If the Air Conditioner Administrator has set running mode then the air conditioner can not ru...

Страница 57: ...n between the real and the setting speed Typhoon protection Indoor evaporator hi tempprotection Low pressure protection Hi pressure protection Inverter module protection Compressor discharge protectio...

Страница 58: ...ound is heard when the system is in cooling operation or at a stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system s...

Страница 59: ...or unit and indoor unit heat exchanger is dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Sunlight directly shine Too much heat resource Outdoo...

Страница 60: ...pressed Check whether the signal transmitter of the remote controller is properly directed to the infrared signal receiver of the indoor unit when the ON OFF button is pressed Directly transmit the s...

Страница 61: ...V 2 www easelectric es...

Отзывы: