A faulty grid 

relay detec-

ted  

The difference 

between INV 

voltage and 

output voltage 

exceeds limit. 

1. Disconnect the inverter from the utility 

grid and the PV array, and reconnect it 

after LED turns off. 

2. If the fault persists, measure the phase 

to phase voltage and phase to zero and 

zero to ground voltage with a multimeter 

to ensure that the voltage is normal and 

the zero to ground voltage value should 

not be greater than 10V. 

3. Disconnect the inverter from the utility 

grid and the PV array, and reconnect it 

after LED turns off.  If this fault is still being 

displayed, please contact service. 

PV voltage 

too high 

When the PV 

voltage of any 

circuit is greater 

than 1020V, it is 

determined as the 

PV voltage is too 

high. 

Check the open-circuit voltages of the 

strings and make sure it is below the 

maximum DC input voltage of the 

inverter. If the input voltage lies within 

the permissible range while the fault 

occurs, please contact the service. 

Surface 

insulation 

resistance 

error 

In the process of 

power on and start-

up, the insulation 

impedance of PV + 

and PV - to ground 

is detected. When 

the detection 

insulation 

impedance is less 

than 200kohm, it is 

judged as insulation 

fault. 

1. If it happens occasionally, it may be 

caused by rainy or humid environment. 

After the fault is eliminated, the inverter 

can resume normal operation without 

other actions. 

2. If there is continuous alarm, please 

check the PV array’s insulation to ground 

and make sure that the insulation 

resistance to ground is greater than 

200KΩ. Otherwise, visual inspection of all 

PV cables and modules. Make sure the 

grounding connection of the inverter is 

reliable. 

If all above are normal, please contact the 

service. 

Ground fault 

circuit 

interrupter 

(GFCI) 

exceeds the 

permissible 

range 

residual current 

over the 

permission range 

1. Make sure the grounding connection 

of the inverter is reliable. 

2. Make a visual inspection of all PV 

cables and modules. 

3. If this fault is still shown, contact the 

service. 

Inverter 

temperature 

too high 

Heat sink and 

internal 

environment 

temperature 

higher than 85 

degree 

Please confirm: 

1. Whether the airflow to the heat 

sink is obstructed. 

2. Whether the installation site is in 

direct sunlight and ambient 

3. temperature around the inverter 

is too high. 

If all above is normal, contact the service. 

25

24

V.

2

V.

2

Utility grid 

disconnected 

inverter 

detected grid 

voltage failed 

1.

2.

If it happens occasionally, it belongs 

to the short-time abnormality of the 

power grid, the inverter will return to 

normal operation after detecting that 

the power grid is normal, and there is 

no need to deal with it. 

If it cannot be recovered for a long 

time, please confirm:

whether the AC circuit breaker is 

disconnected

whether the AC terminal or fuse is in 

good contact 

whether the power supply line is normal 

If this fault is still being shown, contact 

the service. 

10 

Grid voltage 

exceeds the 

permissible 

range  

grid voltage 

exceeds the Safety 

regulations 

1. If it happens occasionally, it belongs to 

the short-time abnormality of the 

power grid, the inverter will return to 

normal operation after detecting the 

normal power grid, and there is no 

need to deal with it. 

2. In case of frequent occurrence but 

automatic recovery, please confirm if 

the grid voltage is outside the 

permissible range due to local grid 

conditions, try to modify the values of 

the monitored operational limits after 

informing the electric utility company 

first.

3. If it cannot be recovered for a long 

time, please confirm: 

· whether the AC circuit breaker is 

disconnected 

·

·

·

whether the AC terminal is in good 

connection

whether the power supply line is normal 

whether the AC cable wiring (such as wire 

length and wire diameter) complies with 

the user manual guidance 

whether the safety regulation settings are 

normal

11 

Grid 

frequency 

exceeds the 

permissible 

range 

grid frequency 

exceeds the safety 

regulations 

1. If it happens occasionally, it 

belongs to the short-time 

abnormality of the power grid, the inverter 

will return to normal operation after 

detecting the normal power grid, and 

there is no need to deal with it.
2. In case of frequent occurrence but 

automatic recovery, please confirm if the 

grid voltage is outside the permissible 

range due to local grid conditions, try to 

modify the values of the monitored 

operational limits after informing the 

electric utility company first.

·

Содержание EINSOLAR5Y

Страница 1: ...iza es EAS ELECTRIC SMART TECHNOLOGY S L U P I San Carlos Camino de la Sierra S N Parcela 11 03370 Redov n Alicante ESPA A Toda la documentaci n del producto Complete documents about the product Docum...

Страница 2: ...EMAS MANTENIMIENTO REINICIO CONDICIONES DE GARANT A 5 5 7 7 5 DESEMBALAJE Accesorios incluidos Resumen del producto INSTALACI N Requisitos de instalaci n Ubicaci n de montaje Montaje PUESTA EN MARCHA...

Страница 3: ...ensi n de CC peligrosa Si se entra en contacto con los cables CC conductores o componentes con tensi n del inversor puede resultar en una descarga mortal 5 El alto voltaje del inversor puede causar de...

Страница 4: ...n una ubicaci n accesible para su funcionamiento y futuros mantenimientos o reparaciones El rendimiento del inversor alcanza su punto m ximo a una temperatura ambiente inferior a 45 C 5 Para instalar...

Страница 5: ...0mm de di metro y 70mm de profundidad 2 Fije la placa de montaje con los tornillos y los pernos de expansi n incluidos en los accesorios de montaje 3 Monte el inversor en la placa de montaje Compruebe...

Страница 6: ...taje y conexi n del cable CA 5 2 1 Puesta en marcha CA 5 2 2 Tipos de interruptor de CA Instale un disyuntor miniatura individual de 2 fases de acuerdo con las siguientes especificaciones Modelo Corri...

Страница 7: ...onexi n del Smart Meter RS485 DRED Puesta en marcha de CC V 2 Paso 1 DRED DRED Meter S R 485 DRED METER RS485 o o Aprox 60m m Paso 2 Paso 3 B A 1 2 Tipo de destornillador Plano 0 4 x 2 5 Conexi n RS48...

Страница 8: ...ctada al inversor y de cerrar el interruptor de CC del inversor compruebe 1 Voltaje de la red Compruebe que el voltaje de la red en el punto de conexi n del inversor coincide con el rango permitido de...

Страница 9: ...sor est n bien conectadas a tierra 8 Voltaje CC Compruebe si la tensi n mayor de circuito abierto de los sistemas fotovoltaicos cumple con el rango permitido 9 Polaridad CC Compruebe si los cables de...

Страница 10: ...an 5 minutos para vaciarse por completo Cuando ocurra un error NO retire la tapa del inversor in situ Una manipulaci n inadecuada puede dar lugar a una descarga el ctrica 19 18 V 2 V 2 9 PAR METROS T...

Страница 11: ...n por corto de salida Integrada Protecci n por sobretensi n de salida Integrada DATOS GENERALES Dimensiones An Al Fo mm 425 346 160 Peso kg 14 Emisi nac stica t pica dB A 25 Interfaz de usuario LED LC...

Страница 12: ...ci n del inversor C digos de error y medidas para solucionarlos Cuando el sistema fotovoltaico no funciona con normalidad siga las siguientes recomendaciones para intentar dar una soluci n r pida al p...

Страница 13: ...te p ngase en contacto con el servicio t cnico 8 Temperatura del inversor demasiado alta Temperatura del disipador de calor y del entorno interno superior a 85 grados Compruebe 1 Si la ventilaci n del...

Страница 14: ...La tensi n de bus es superior a 1030V Compruebe las tensiones de circuito abierto de los strings y aseg rese de que est n por debajo de la tensi n de entrada de CC m xima del inversor Si la tensi n de...

Страница 15: ...be que los cables est n bien conectados a tierra AVISO EL DISIPADOR DE CALOR PUEDE PROVOCAR LESIONES Cuando el inversor est en marcha el disipador de calor puede alcanzar los 60 C Desconecte todos los...

Страница 16: ...s de cualquier naturaleza 8 Aver as producidas por factores externos como alteraciones de corriente sobrecargas el ctricas suministro de voltaje excesivo o incorrecto radiaci n y descargas electrost t...

Страница 17: ...ERS TROUBLESHOOTING SYSTEM MAINTENANCE RESTARTS GUARANTEE CONDITIONS UNPACKING Scope of delivery Product overview INSTALLING Installation requirement Mounting location Mounting COMMISSIONING Safety in...

Страница 18: ...rous output in DC voltage Contacts with the DC wires conductors and live components in the inverter may result in lethal shocks 5 High voltages in inverter could cause lethal electrical shocks Before...

Страница 19: ...inverter in an accessible location for operation future maintenance and service The inverter performance peaks at ambient temperature lower than 45 C 5 When installing in residential or domestic envir...

Страница 20: ...racket as a template and drill holes of 10mm diameter and 70mm depth 2 Fix the mounting bracket with the screws and expansion bolts packed in mounting accessories 3 Attach the inverter to the mounting...

Страница 21: ...embly and Connection 5 2 1 AC Commissioning 5 2 2 AC Switch Types Please install an individual 2 stage miniature circuit breaker according to the following specifications Model Maximum output current...

Страница 22: ...the Datalogger from package 1 Unscrew the cap in COM1 port 2 Plug the Datalogger in and tighten For user guidance and configuration of Datalogger please refer to the corresponding Wi Fi Stick Guide m...

Страница 23: ...ck before switching on any voltage resources connected to the inverter and closing inverter s DC switch 1 Grid Voltage Check the grid voltage at point of connection at the inverter complies with permi...

Страница 24: ...ltage and grid conditions meet the requirements of inverter startup 6 Cables Check if all cables are reliably connected Check if the connections are effective while the insulations are undamaged 7 Gro...

Страница 25: ...s need 5 minutes to be completely de energized When an error occurs DO NOT remove the cover of the inverter onsite Improper operations and attempts may induce electric shock 19 18 V 2 V 2 9 TECHNICAL...

Страница 26: ...t Protection Integrated Output Over Voltage Protection Integrated GENERAL DATA Dimensions W H D mm 425 346 160 Weight kg 13 7 Noiseemission typical dB A 25 User Interface LCD LED or LED DC connection...

Страница 27: ...rective Measures When the PV system does not operate normally we recommend the following solutions for quick troubleshooting If an error occurs the Error code will be displayed on the inverter s scree...

Страница 28: ...ree Please confirm 1 Whether the airflow to the heat sink is obstructed 2 Whether the installation site is in direct sunlight and ambient 3 temperature around the inverter is too high If all above is...

Страница 29: ...his fault is still being displayed please contact the service Master CPU communicate with slave CPU abnormal 15 Bus voltage too high Bus voltage is greater than 1030V Check the open circuit voltages o...

Страница 30: ...y grounded Half a year after first commissioning Annually OR Half a year NOTICE HEAT SINK MIGHT INDUCE INJURY When the inverter is operating the heat sink might exceed 60 C Please disconnect all elect...

Страница 31: ...Loss or damage to software or information media 9 Faults produced by external factors such as current disturbances electrical surges excessive or incorrect voltage supply radiation and electrostatic...

Отзывы: