4.2 Mounting Location
1. DO NOT mount the inverter near any inflammable materials.
2. DO NOT mount the inverter near any explosive materials.
3. DO NOT mount the inverter on tilting surface over 15° backwards.
Please mount the inverter on a vertical wall surface.
4. DO NOT mount the inverter on any surfaces tilting forward or to either
sides.
5. DO NOT mount the inverter on a horizontal surface.
6. For easy installation and operation, please mount the inverter on a
height that the display could match eye level.
7. The bottom side where all commissioning terminals are equipped MUST
always point downwards.
4.3 Mounting
1.
Use the mounting bracket as a template and drill holes of 10mm
diameter and 70mm depth.
2.
Fix the mounting bracket with the screws and expansion bolts
packed in mounting accessories.
3.
Attach the inverter to the mounting bracket.
4.
Check both sides of
the
heat sink and ensure the inverter is stably
attached.
5.
Use M5 screws (with T25 screwdriver, torque: 2.5Nm) to attach the
heat sink fins to the mounting bracket.
6.
It is recommended to attach the anti-theft lock to the inverter. Lock
diameter
φ
4-5.5mm recommended.
4.4 Installing the PE cable
1.
Insert the grounding conductor into the suitable terminal lug and
crimp the contact.
2.
Thread the M5 * 13 screw through the terminal lug.
3.
Tighten it firmly into the housing (screwdriver type: T25, torque:
2.5Nm).