Figure 19. Superheat Measurements for SC, SD and SCW Compressor Units
(SC Model shown).
10.
Using an accurate temperature indicator, read the suction temperature at the
compressor suction port.
Read the suction pressure at the access port on the LP
gage.
11. Enter the Pressure-Temperature Table in Figure 20 and for the suction pressure read
on the LP gage, determine the saturation temperature (evaporating temperature) from
the chart, interpolating if necessary.