PHXTI-IM (05/13)

 

 

Page 7

 

B.  Refrigerant Connections 

 

The refrigerant connections are shown in Figure 3.  Each connection is 5/8 inch OD copper tube.  
The refrigerant line connections are brazed as follows: 

1.  Clean and deburr the copper stub outs and the field supplied fittings that will make the 

connections from the refrigeration system. 

2.  Use 15% silver brazing alloy to seal the refrigeration connections. 

3.  Make provisions to use the nitrogen brazing technique as described below to braze the 

refrigerant joints. 

 

4.  Before brazing the refrigerant joints, protect the SWAGLOK

®

 fittings illustrated in Figure 3 by 

wrapping each joint with a wet cloth, and further protect it from direct torch flame with an 
inflammable shield as shown in Figures 4, 5 and 6. 

Содержание PHXTI Series

Страница 1: ...rthlinked Technologies Inc EarthLinked Series PHXTI Pool Heat Exchangers Installation Manual CONTENTS PAGE Pre Installation 3 Installation 3 Water Connections 4 Refrigerant Connections 7 Freeze Protec...

Страница 2: ...CR equipment and in accordance with instructions set forth in this manual Earthlinked Technologies shall not be liable for any defect unsatisfactory performance damage or loss whether direct or conseq...

Страница 3: ...eat exchanger is sold as a system component and must be sized and properly matched to other system components to provide the anticipated performance and safe operation of the system 2 Installation The...

Страница 4: ...changer is shown in Figure 2 The heat exchanger is installed downstream of the filter and upstream of the water conditioning system The heat exchanger shall be no more than 10 feet from the heat pump...

Страница 5: ...heat exchanger and the OD surfaces on the water supply and return PVC pipes 2 Clean the same surfaces in item 1 with PVC Cleaner Oatey 30782 or equivalent and allow to dry 3 Apply PVC Cement Oatey 30...

Страница 6: ...PHXTI IM 05 13 Page 6 Figure 3 Heat Exchanger Refrigerant Connections...

Страница 7: ...at will make the connections from the refrigeration system 2 Use 15 silver brazing alloy to seal the refrigeration connections 3 Make provisions to use the nitrogen brazing technique as described belo...

Страница 8: ...PHXTI IM 05 13 Page 8 Figure 4 Wrap SWAGLOK Joints...

Страница 9: ...PHXTI IM 05 13 Page 9 Figure 5 Apply Flame Retardant Shield...

Страница 10: ...PHXTI IM 05 13 Page 10 Figure 6 Braze Joints...

Страница 11: ...the filtration system continuously through the freeze period Generally during a light freeze circulating water will not freeze In areas where freezing conditions are prevalent and more severe implemen...

Страница 12: ...PHXTI IM 05 13 Page 12 D Warranty All warranty claims shall be handled directly through AquaCal AutoPilot Inc...

Отзывы: