Product Manual DA110
EAE KNX DALI Gateway
DA110 R2.0
©
EAE Technology
www.eaetechnology.com
Page 6 / 21
2.2. Communication Object Descriptions
No
Function
Name
DPT
Length Flags
0
In operation
General
1.002
1 bit
CT
This object is used to report that device is still alive and connected to the KNX line by sending cyclic 1 bit
telegrams. If a telegram is not received, device may be defective or KNX cable would be intercepted.
-
Object will be activated if “Device alive operation active” parameter in the General tab is selected as
“enable”.
-
Telegram type (ON or OFF) can be selected via “In operation bit” parameter in General parameters tab.
-
Cyclic period of transmitted telegrams can be selected via “In operation send interval” parameter in General
parameters tab.
1
Enable manual operation
General
1.003
1 bit
CRW
This object is used for enabling or disabling the manual operation button located on the device. If the manual
operation disabled, manually switching or dimming of the connected DALI devices is not possible.
Furthermore, the status of manual operation can be read via this communication object.
-
Value of the object will be “1” after an ETS download if the "Enable manual operation" parameter in General
tab is selected as 'enable'. Value will be “0” if parameter is selected as “no”.
(value “1” = manual operation enable, value “0” = manual operation disable)
2
New devices addressing
General
1.010
1 bit
CW
This object is used to start adressing the all DALI devices randomly. If there is even addressed devices before,
they will be re-addressed again. Please send “enable(1)” to this group object to start this function.
3
Field capture
General
1.010
1 bit
CW
This object is used to read and save all DALI devices to DA110 device which can be found by scan. Un-
addressed devices will be addressed and conflicted addresses will be resolved. Please send “enable(1)” to this
group object to start this function.
NOTE: If statuses are wrong or zero please perform this operation.
4
Request all statues
General
1.010
1 bit
CW
This object is used to read all status by triggering this object when needed. Status information will be sent via
Coded objects (if activated) and via Switch/Status or Set brightness value/Status object(if activated). Please
send “enable(1)” to this group object to start this function.