2.2. Communication Object Descriptions 

No 

Function 

Name 

DPT 

Length  Flags 

In operation 

General 

1.002 

1 bit 

CT 

This object is used to report that device is still alive and connected to the KNX line by sending cyclic 1 bit 

telegrams. If a telegram is not received, device may be defective or KNX cable would be intercepted. 
-

 

Object will be activated if  “Device alive operation active”  parameter in the General tab is selected as 

“enable”.  

-

 

Telegram type (ON or OFF) can be selected via “In operation bit” parameter in General parameters tab. 

-

 

Cyclic period of transmitted telegrams can be selected via “In operation send interval” parameter in General 

parameters tab. 

Enable manual operation 

General 

1.003 

1 bit 

CRW 

This object is used for enabling or disabling the manual operation button located on the device. If the manual 

operation disabled, manually switching or dimming of the connected DALI devices  is not possible. 

Furthermore, the status of manual operation can be read via this communication object.  

-

 

Value of the object will be “1” after an ETS download if the "Enable manual operation" parameter in General 

tab is selected as 'enable'. Value will be “0” if parameter is selected as “no”. 

(value “1” = manual operation enable, value “0” = manual operation disable) 

New devices addressing 

General 

1.010 

1 bit 

CW 

This object is used to start adressing the all DALI devices randomly. If there is even addressed devices before, 

they will be re-addressed again. Please send “enable(1)” to this group object to start this function. 

Field capture 

General 

1.010 

1 bit 

CW 

This object is used to read and save all DALI devices to DA110 device which can be found by scan. Un-

addressed devices will be addressed and conflicted addresses will be resolved. Please send “enable(1)” to this 

group object to start this function.  
NOTE: If statuses are wrong or zero please perform this operation. 

Request all statues 

General 

1.010 

1 bit 

CW 

This object is used to read all status by triggering this object when needed. Status information will be sent via 

Coded objects (if activated) and via Switch/Status or Set brightness value/Status object(if activated). Please 

send “enable(1)” to this group object to start this function.  

 

 

Содержание DA110

Страница 1: ...Order Number 48107 EAE KNX DALI Gateway Product Manual DA110...

Страница 2: ...ion 2 1 2 Technical Data 3 1 3 Connection Example 4 1 4 Operation and Display 4 2 Communication Object Information 5 2 1 Communication Object Table 5 2 2 Communication Object Descriptions 6 3 Paramete...

Страница 3: ...atures are listed below Maximum 64 DALI devices e g electronic ballast transformer can be connected to DALI output DA110 enables to control 64 DALI devices individually and can store 16 different ligh...

Страница 4: ...1 5 mm2 Max 300 m 0 75 mm2 Max 150 m 0 5 mm2 Max 100 m Installation 35mm mounting rail EN 60715 Operating elements Programming LED and button Green LED Yellow LED Red LED Manual button Test button Phy...

Страница 5: ...fault is present Lamp fault ballast fault Fast Blink Initialization is active Manual LED 9 Lights up when manual control is activated by pressing manual button Manual Button 10 Activate Deactivate man...

Страница 6: ...1 Lamp fault Feedback 1 005 1 Bit CRT 12 Device fault Feedback 1 005 1 Bit CRT 13 Mains power failure status Feedback 1 005 1 Bit CRT 14 Scene 8 bit Scene 17 001 1 Byte CW 15 0 Scene 1 1 Scene 2 Scene...

Страница 7: ...manual operation can be read via this communication object Value of the object will be 1 after an ETS download if the Enable manual operation parameter in General tab is selected as enable Value will...

Страница 8: ...if parameter is selected as after change Feedback will be sent on both occasions if the parameter is selected as after change or request Bit numbers and data which they represented is explained below...

Страница 9: ...of whether a device or a group is selected Object will be activated if Enable Coded status switch object parameter in Feedback tab is selected as enable Feedback will be sent only after a request if...

Страница 10: ...information of whether a device or a group is selected Object will be activated if Enable Coded status brightness value object parameter in Feedback tab is selected as enable Feedback will be sent onl...

Страница 11: ...ill be activated if Enable Coded faults object parameter in Feedback tab is selected as enable Feedback will be sent only after a request if transmit mode parameter in Feedback tab is selected as afte...

Страница 12: ...nly after a value change if parameter is selected as after change Feedback will be sent on both occasions if the parameter is selected as after change or request value 0 gateway supply works properly...

Страница 13: ...mains connected to DALI line NOTE Overvoltage sense circuitry on the DALI line is triggered on voltages above 40V So any voltage above 40V is considered as mains 14 Scene 8 bit Scene 17 001 1 byte CW...

Страница 14: ...ballasts 25 Broadcast Relative dimming Broadcast 3 007 4 bit CW This object is used to dim all connected DALI ballast The brightness value is changed in the defined direction with the parameterized sp...

Страница 15: ...ed to switch DALI device 1 64 ON or OFF 44 Group 1 Brightness value Dali Device 1 64 5 001 1 byte CWU Set brightness value Status after change CWTU Set brightness value Status after request CRWU Set b...

Страница 16: ...elected enable following parameters come up In operation value true false Telegram value can be selected as 1 or 0 Operation send interval sec 1 300 65535 Telegram value is sent cyclically according t...

Страница 17: ...e dimming commands separately If these parameters are selected no then it is not possible to switch on or off the lighting fixtures via brightness value 1 byte or relative dimming 4 bit objects of the...

Страница 18: ...y device that has a fault lamp is present or not Enable Device fault object enable disable Parameter enables Fault ballast object This object is used for reporting whether there is any offline or malf...

Страница 19: ...applied to the mains line of DA110 device Transmit mode description is the same for all parameters in Feedback tab But selections can be made independently for each parameter Transmit mode after reque...

Страница 20: ...change Parameter defines the brightness value of ballasts on DALI line voltage loss Lamp values on DALI voltage recovery 0 0 100 255 no change Parameter defines the brightness value of ballasts on DA...

Страница 21: ...us of the group can be read from this object itself or separate status object No response option disables the Read flag of object After request mode status object only response to a read request After...

Страница 22: ...ct as well Activate scenes 1 16 no yes Scene count can be selected in this page This page only activates the DALI device control objects Unselected device adresses can still be controlled in scenes Al...

Отзывы: