Product Manual DA110
EAE KNX DALI Gateway
DA110 R2.0
©
EAE Technology
www.eaetechnology.com
Page 10 / 21
No
Function
Name
DPT
Length Flags
8
Coded faults
Feedback
237.600
2 byte CWT
This object is used to get fault data of a DALI group or an individual DALI device. In order to make a read
request, a write should be made to object with read/response bit is set.
Object consists of two bytes. High byte of telegram contains fault data and low byte contains DALI address of
subjected device or group number, information of whether telegram is a status request or sent status and
information of whether a device or a group is selected.
-
Object will be activated if “Enable “Coded faults” object” parameter in Feedback tab is selected as “enable”.
-
Feedback will be sent only after a request if “transmit mode” parameter in Feedback tab is selected as “after
request” or only after a value change if parameter is selected as “after change”. Feedback will be sent on
both occasions if the parameter is selected as “after change or request”.
Bit numbers and data which they represented is explained below;
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Byte
Bit Field
Description
1
Bit 0 - 5
DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6
Individual device or group flag: '1' = device address, '0' = group number
Bit 7
Read or response flag: '1' = read, '0' = response
2
Bit 8
Device is offline or malfunction flag: '1' = failure '0' = no failure
Bit 9
Lamp failure flag: '1' = failure '0' = no failure
Bit 10
Reserved
Bit 11 - 15 Reserved