37
38
Region
Default Value
V
V1
V
V2
V
V3
V
V4
Australia A Voltage
207 V
220 V
240 V
258 V
Inverter reactive
power
level
(Q)% of
S
rated
44%
supplying
0%
0% 60%
absorbing
Australia B Voltage
205 V
220 V
235 V
255 V
Inverter reactive
power
level
(Q)% of
S
rated
30%
supplying
0%
0% 40%
absorbing
Australia C Voltage
215 V
230 V
240 V
255 V
Inverter reactive
power
level
(Q)% of
S
rated
44%
supplying
0%
0% 60%
absorbing
New
Zealand
Voltage
207 V
220 V
235 V
244 V
Inverter reactive
power
level
(Q)% of
S
rated
60%
supplying
0%
0% 60%
absorbing
Procedures to enable or disable the Volt-var Response Mode:
Step1: go to ‘All Set Enable’ in the menu of ‘TECHNICAL SET’ and turn the
status to ‘ON’.
Step2: go to ‘Special Func’ and then go to ‘QU Curve’
Step3: enable or disable the ‘Volt-var Response Mode’ by changing the status
to ‘ON’ or ‘OFF’.
6.2.5.8.3 Volt-watt Response Mode
The PU Curve is enabled by default. The volt-watt response mode varies the
maximum active power output level of the inverter in response to the voltage
at its grid-interactive port. The diagram below is the response curve required
for the volt–watt response according to the standard of AS/NZS 4777.2:2020.
PU CURVE
ON
NOTE
: This operation is for maintenance personnel only. Password
is required to access this part!