background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)20 8740 4200 
Document No. IS 4501      Issue E                     27-11-09                      

Sheet 6 of 6

 

 

 
 
 
The IS-A105N Sounder has also been approved to the IECEx 
scheme.  
 
The  installation  requirements  for  IS-A105N  sounders 
approved  to  the  IECEx  scheme  are  the  same  as  the 
installation requirements for IS-A105N sounders approved to 
the ATEX directive. 
 
Certificate No. 

IECEx SIR 04.0038X 

 
 
Marking:  

Ex ia IIC T4 Ga  (Ta = -40ºC to +60ºC) 

 
 
Standards: 

IEC 60079-0:2004 

Edition 4

 

 

 

IEC 60079-11:2006 

Edition 5

 

IEC 60079-26:2006 

Edition 2

 

 

CONDITIONS  OF  CERTIFICATION  (as  stated  on  the  IECEx 
Certificate of Conformity IECEx SIR 04.0038X) 
 

 

1.  The equipment shall only be supplied via Terminals 

+ w.r.t. Terminals - from a certified barrier having a 
maximum open circuit voltage Uo that is less than or 
equal to 28 V and a maximum short circuit current Io 
that  is  less  than  or  equal  to  93  mA,  where  Io  is 
resistively limited.  

 

2.  The total capacitance connected to ter wrt – 

(i.e.  the  capacitance  of  the  cable  plus  any  other 
capacitance) shall not exceed 83nF. 

 
3.  The  equipment  has  an  ingress  protection  rating  of 

IP66;  however,  if  it  has  been  supplied  without  a 
cable entry  device,  then  the  user  shall  ensure  that 
the  device  that  is  fitted  will  provide  an  ingress 
protection  that  is  appropriate  to  the  environment  in 
which it is installed i.e. IP20 or better. 

 

4.  The enclosure is non-conducting and may generate 

an  ignition-capable  level  of  electrosatic  charges 
under  certain  extreme  conditions.  The  user  should 
ensure  that  the  equipment  is  not  installed  in  a 
location  where  it  may  be  subjected  to  external 
conditions  that  might  cause  a  build-up  of 
electrostatic  charges  on  non-conducting  surfaces, 
additionally,  cleaning  of  the  equipment  should  be 
done only with a damp cloth. 

 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
The IS-A105N Sounder has also been FM Listed. 
 
 
Marking:           IS Class I, Zone 0, AEx ia IIC T4 
 
 

          IS Class I, Division 1, Groups A, B, C, D 

 
See  the  Control  Drawings  D  4528  Sheets  1  and  2  for 
installation details and entity parameters. 
 
 
 
The  IS-A105N  sounders  are  marked  with  the  certification 
requirements for the ATEX, IECEx and FM approvals. 

 

e

2S

european safety sys tems ltd. 

SIRA 04ATEX2301X

0518

IS-A105N Sounder

London W3 7QH UK
www.e2s .c om

Year / Serial N o.  
   09 / 1S000001

WARNINGS:

 

IECEx SIR 04.0038X

Term. + w.r.t. Term. -  Ui = 28V  Ii = 93mA  
                                    P i = 660mW   Ci = 0   Li = 0
Term. S2&S3 w.r.t. Term. -   Ui =  28V  Ii = 0mA

FM

APPROVED

To avoid a possible electrostatic

charge only clean with a damp cloth 

To prevent ignition of flammable or combustible
 atmospheres, disconnect power before servicing

 

Substitution of components may impair safety 

IS Class I, Zone 0, AEx ia IIC T4
IS Class l, Division 1, Groups A, B, C, D

II 1G   Ex ia IIC T4 Ga (-40ºC <=Ta<= +60°C)

Control Drawing No. D 4528

 

 

 

IECEx Certification 

FM Approval 

Отзывы: