background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)20 8740 4200 
Document No. IS 4501      Issue E                     27-11-09                      

Sheet 3 of 6

 

intrinsically safe relay or a galvanic isolator, all of which must 
have  been  certified  by  an  EC  Notified  Body.      Only  diode 
return barriers with a  voltage drop of less than 0.9V may be 
used.  Alternatively,  these  terminals  may  be  connected 
directly  to  a  mechanically  activated  switch  within  the 
hazardous area. 
 

+     +     -      -

     S2    S3

1   2   3   4   5   6    

Input Terminals

Volume

Control

Tone Setting
Switches 1-6

ON

 

 

 

Fig 2  Location of field terminals and controls. 

 

 
 

4.5   Other intrinsic safety certifications 

Please  contact  European  Safety  Systems Ltd. for details  of 
non-European intrinsic safety approvals. 
 

 

5) 

Installation 

 

IS-A105N  sounders  should  only  be  installed  by  trained 
competent personnel. 

 
5.1 Mounting

 

The  IS-A105N  sounder  may  be  secured  to  any  flat  surface 
using  the  two  7mm  diameter  fixing  holes.  The  enclosure 
provides  IP66  protection  and  is  suitable  for  installation  in 
exterior locations providing it is positioned so that water can 
not collect in the horn, and the cable entry is sealed. 

 
5.2  Installation procedure 

 

a.  Secure the IS-A105N sounder to a flat surface via the 

two 7mm dia fixing holes in the mounting feet. 

 
b.  Remove  the  front  of  the  sounder  by  unscrewing  the 

four captive ‘A’ screws and pulling the front away from 

the enclosure.  

 
c.  Fit  a  20mm  cable  gland  or  conduit  entry  into  the 

untapped hole in the enclosure and connect the field 

wiring to the appropriate sounder terminals as shown 

in section 6 and fig 2 of this manual. The power supply 
ter and - are duplicated so that sounders may 

be connected in parallel, or an end of line monitoring 

resistor may be fitted. 

 

d.  Select the required output tone by positioning the six 

switches as shown in Table 1 and Fig 2.  

 

e.  Apply  power  to  the  sounder  and  adjust  the  internal 

volume control to provide the required sound level. 

 

f. 

Replace the front of the sounder and tighten the four 

‘A’ screws. 

 

6) 

Electrical System Design For Installation In 
Hazardous Areas Using Zener Barriers

 

 

6.1  Single stage alarm  

If  the  control  switch  is  in  the  positive  supply,  or  the  power 
supply is being turned on and off, only a single channel Zener 
barrier is required as shown in Fig 3. This circuit may also be 
used  if  the  sounder  is  being  controlled  by  a  mechanically 
activated switch on the hazardous area side of the barrier. 

 

Power
Supply

+

0V

Barrier

On/Off

IS-A105N

Sounder

+

-

28V 93mA

Positive

Hazardous Area

Safe Area

 

 

Fig 3  Single stage alarm using single channel barrier. 

 
 
If the control switch must be in the negative supply, the circuit 
shown in Fig 4 may be used. Any diode return barrier certified 
Ex  ia  by  a  EC  Notified  Body  may  be  used,  providing  its 
voltage drop is less than 0.9V.  
 

Power
Supply

+

0V

Barrier

IS-A105N

Sounder

+

-

28V 93mA

Positive

Hazardous Area

Safe Area

Diode  Return

    Barrier

On/Off

 

 

Fig 4  Single stage alarm using two channel barrier. 

 
 

6.2  Multi-stage alarm 

Connecting  terminal  S2  to  0V  activates  the  second  stage 
alarm, and similarly terminal S3 for the third stage alarm. Fig 
5 shows how the diode return barriers may be used. If only 
two  stages  of  alarm  are  required  the  third  stage  barrier 
should be omitted, the 28V 93mA barrier and the single diode 
return channel may then be contained in one package. 

Power
Supply

+

0V

Barrier

IS-A105N
Sounder

+

-

28V 93mA
Pos itive

H azardous Area

Safe Area

D io de Re turn

    Bar rier

2nd Stage

On/Off

D io de Re turn

    Bar rier

3rd Stage

S2

S3

 

Fig 5  Multi stage alarm using Zener barriers. 

Отзывы: