Config. 

Voltage 

Configuration Description 

Features  

Product 
Option 
Identifier 

See documents D190-06-651 for DC schematic diagrams.

 

1a 

DC 

Single Stage Configuration 

 

Line monitoring 

 

Positive Switching 

1b 

DC 

Two Stage Configuration 

 

Common Negative  

 

Positive Switching 

1c 

DC 

Three/Four Stage Configuration 

 

Common Negative  

 

Positive Switching 

DC 

Three/Four Stages. Voltage Free 2nd, 3rd & 
4th Stage Activation Configuration 

 

Common Positive 

 

Customer  Set  H1  &  H2  to  Negative 
Switching  

Table 3: Summary of Wiring Options. 

 
 

9)  End of Line Monitoring (DC Units) 

 
All DC units have a blocking diode fitted in their supply input 
lines.  An  end  of  line  monitoring  diode  or  an  end  of  line 
monitoring resistor can be connected across the +ve and 

ve 

terminals in the flameproof chamber. 
 
If  an  end  of  line  resistor  is  used  it  must  have  a  minimum 
resistance value of 3k3 ohms and a minimum wattage of 0.5W 
or a minimum resistance value of 500 ohms and a minimum 
wattage of 2W. 

 

The resistor must be connected directly across the +ve and -
ve  terminals  as  shown  in  the following  drawing.  The  resistor 
leads should be kept as short as possible. 
 
SIL2  line  monitoring module  product  version:  see  section  19 
for standard default values and product coding. See document 
D190-06-651 for associated wiring diagram.` 

 

 

Figure 11: End of Line Resistor placement. 

 
Note that the maximum forward polarity monitoring voltage is 
6V.  A  monitoring  voltage  greater  than  6V  may  activate  the 
alarm horn sounder and the 2nd, 3rd or 4th stages.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

10) Maintenance, Overhaul and Repair

 

 

Maintenance,  repair  and  overhaul  of  the  equipment  should 
only  be  carried  out  by  suitably  qualified  personnel  in 
accordance with the current relevant standards: 
 

EN60079-19/IEC60079-19  

 

Explosive atmospheres 

 Equipment repair, overhaul and 

reclamation 
 
EN 60079-17/IEC60079-17  

 

Explosive atmospheres 

 Electrical installations inspection 

and maintenance 
 

Flameproof  threaded  joints  and  cemented  joints  are  not 
permitted to be repaired. 
 
Units  must  not  be  opened  while  an  explosive  atmosphere  is 
present. 
 
If  opening  the  unit  during  maintenance  operations  a  clean 
environment must be maintained and any dust layer removed 
prior to opening the unit. 
 
Electrostatic charging hazard - Clean only with a damp cloth. 
 
 
 
 
 
 
 
 
 
 
 

Содержание GNExS2FDC024-S

Страница 1: ...evel P3 dB A P2 P3 P2 P3 Max Nom Max Nom GNExS2FDC024 S 24Vdc 20 28Vdc 324mA 740mA 324mA 740mA 120 115 123 118 GNExS2HDC024 S 24Vdc 20 28Vdc 324mA 740mA 324mA 740mA 124 119 127 122 Max Tone 4 Nom Tone...

Страница 2: ...cate No SIRA 13ATEX1139X IECEx SIR 13 0029X CSAE 21UKEX1558X Epsilon x Equipment Group and Category II 2G CE Marking and Notified Body No 2813 UKCA Marking and Notified Body No 0518 4 Zones Gas Group...

Страница 3: ...clean and that they have not been damaged during installation Ensure that the O ring seal is in place and undamaged When fitting the flameproof cover ensure the thread is engaged correctly Fully tigh...

Страница 4: ...ranching point temperatures may exceed 70 C at entry point 80 C at branching point Therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as s...

Страница 5: ...switching Figure 9 Stage Switching Polarity 8 3 Tone Selection The ExS Alarm Horn Sounders have 64 different tones that can be selected independently for the first and second stage alarms The tones ar...

Страница 6: ...ms and a minimum wattage of 2W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing The resistor leads should be kept as short as possible SIL2 line...

Страница 7: ...SIL 2 Sounder Unit Monitors Standby mode and Active mode Health status of power supply Sounder correct function and tone pattern The SIL 2 sounder operates as part of a SIL 2 system The sounder will a...

Страница 8: ...quire further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must n...

Страница 9: ...ounder check on pattern generation and signal output checks Important Only tones use tones that are stated as SIL 2 approved for the SIL 2 application Ensure that the unit is set to one of these tones...

Страница 10: ...rom the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Sounder power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2...

Страница 11: ...multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single alarm horn sounder For more information see manual D197 00 651 IS available from t...

Страница 12: ...ion B pins 2 3 linked Places power supply terminal Fault resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 17 J2 Header pin positions Fault Resistor FR 15 4 SIL 2 Hard Reset Function...

Страница 13: ...nput GNExS2FDC024 S GNExS2HDC024 S Failure to Sound Integrity in respect of failure to release SIL 2 Total Failure rate 0 447 pmh hazardous failure rate revealed 0 443 pmh hazardous failure rate unrev...

Страница 14: ...The values of resistors available are shown in table 6 below Code Resistor Value Default resistor coding as follows GNExS2FDC024AB1S1R AFZ Example of a custom requirement resistor coding GNExS2FDC024...

Страница 15: ...0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1...

Страница 16: ...OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve EOL EOL S2 EOL S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT...

Страница 17: ...S NTS SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED Stage 2 ve Common ve IN Common ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 OF 2 2 EOL S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUP...

Страница 18: ...y No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T...

Страница 19: ...te and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Страница 20: ...ipment II 2G Ex db IIB or IIC T3 T4 T5 or T6 Gb Standards applied EN 60079 0 2018 EN 60079 1 2014 A C 2018 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6...

Отзывы: