1) Product Table
Unit Type Code
Nominal
Input Voltage
Voltage Range
Nominal
Input Current
Max.
Current
Sound
Pressure Level
dB(A)
Max*
Nom
.†
GNExS1RDC024
12Vdc
10-30Vdc
221mA
221mA
110
105
24Vdc
185mA
GNExS1RDC048
48Vdc
38-60Vdc
115mA
221mA
110
105
GNExS1RAC230
115Vac
100-260Vac 50/60Hz
73mA
80mA
110
105
230Vac
48mA
GNExS1FDC024
12Vdc
10-30Vdc
221mA
221mA
115
110
24Vdc
185mA
GNExS1FDC048
48Vdc
38-60Vdc
115mA
221mA
115
110
GNExS1FAC230
115Vac
100-260Vac 50/60Hz
73mA
80mA
115
110
230Vac
48mA
*Max = Tone 4
†
Nom. = Tone 44
The table shows the input current taken by the various sounders.
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage.
Nominal current at nominal voltage.
Max rated current at worst case supply voltage.
Table 1: Electrical Ratings.
Ensure the system power supply is capable of providing the maximum current required for all sounders. Review associated cable size,
length and quantity of sounders on each circuit.