16) Maintenance, Overhaul, Repair and
Cleaning
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
For ATEX / IECEx / UKEx
EN 60079-19
Explosive atmospheres – Equipment
IEC 60079-19
repair, overhaul and reclamation
EN 60079-17
Explosive atmospheres – Electrical
IEC 60079-17
installations inspections and maintenance
Electrostatic charging hazard – clean only with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
For US & CEC Class / Div / Zone
UL 60079-19
Explosive atmospheres - Equipment repair,
overhaul and reclamation
UL
60079-17
Explosive atmospheres - Electrical
installations inspection and maintenance
17) SIL 2 Reliability Data
Reliability and Functional safety IEC/EN61508 which has
been assessed and is considered suitable for use in low
demand safety function:
Random Hardware Failures and Systematic Failures
(route 2H)
As an unvoted item (i.e. hardware fault tolerance of
0) at SIL 2
The product was assessed against failure modes:
Failure to close a contact when the call point is
struck with specified force
Failure to open a contact when the call point is
struck with specified force
Spurious output despite no input
Integrity in respect of failure to close
SIL 2
System Type
A
Hardware Fault Tolerance
0
Safe Failure Fraction (credible claim)
75%
PFD (hazardous failure)
2.3 x 10
-3
Proof Test Interval
Up to 1 year