The GNExCP7 Call Point range can be supplied with the 
following types of adapters: 
M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

 

It is important to note that stopping plugs cannot be fitted 
onto adapters, only directly onto the M20 entries. 

 

Any other adapters used must be suitably rated and ATEX / 
IECEx / UKEx or NEC/CEC certified adapters. 
 
 
 

12) Cable & Wiring Connections 

 

The units come with two options. 
 
A DIN rail version which has 8-way connection and allows for 
limited wiring of EOL devices by customer, or, full pre-wired 
configurations if outlined with order to E2S. 
For full wiring details see wiring diagrams D202-06-211 
 
The PCB Terminal Version has a 6-way connector but is 
designed to allow for full customer configuration with Series 
and EOL devices in a number of wiring configurations. E2S 
can also configure unit at time of order to E2S 
For full wiring details see wiring diagrams D202-06-212 
 
For EOL and Series device limitations and configurations see 
Section 15. Fitting can be requested by E2S at the order 
stage or added to the correct terminal blocks afterward. All 
devices must comply with the requirements stipulated in 
section 15. 
 
Electrical Connections are to be made into the terminal 
blocks using solid or stranded wire. 
Wires having a cross sectional area between 0.5 mm² to 
2.5mm² (AWG 20 – 14) can be connected to each terminal 
way.  
 
In most configuration an input and output wire can be fitted to 
individual terminals, where these are more complex and if 
fitting 2-off wires to one terminal way, the sum of the 2-off 
wires must be a maximum cross sectional area of 2.5mm². 
 
Strip wires to 8mm. Wires may also be fitted using ferrules. 
 
DIN Rail Terminals: 0.51 Nm / 4.5 Lb-in; 
Connector Block Terminals: 0.87 Nm / 7.7 Lb-in; 
 
PCBA Main Terminals: 0.45 Nm / 4.0 Lb-in; 
PCBA EOL and Series (1 & 2) Terminals: 0.38 Nm / 3.4 Lb-in 
 
When connecting wires to the terminals great care should be 
taken to dress the wires so that when the cover is inserted 
into the chamber the wires do not exert excess pressure on 
the terminal blocks. This is particularly important when using 
cables with large cross-sectional areas such as 2.5mm². 

 
 

13) Testing unit operation 

 

The break glass unit can be tested without the need to 
break/replace the frangible glass element.  
A test key (Plastic Key Supplied with unit) is used to 
mechanically drop the glass down activating the switch.  
 

 

 
The test key is inserted in the test cam and rotated clockwise 
by an angle of 90º the glass element will visibly drop down in 
the viewable window.  
 
The call point switch will now change over its contacts to 
operate the alarm. 
 
Once testing is complete the unit needs to be reset, the test 
key is rotated back anticlockwise 90º to its original vertical 
position. The glass element should now raise up so it is level 
again (horizontal) in the viewable window. 
 

 

1.                                       2.                          3. 
Insert test 

 

Hold in                 Rotate back  

Key rotate              

position                anticlockwise  

clockwise               

during                   to reset 

60º                         

test 

 
 

14) Replacement of glass element 

 
If the break glass unit has been operated the broken glass 
element can be quickly replaced. 
 
The break glass cover plate is removed by unscrewing the 4 
off M4 cap head screws attaching it.  
 

 
 

 

Содержание GNExCP7-BG-S

Страница 1: ...G D GNExCP7 BG D L 48Vdc Max 1 0A Max 24Vdc Max 3 0 Max GNExCP7 BG S C GNExCP7 BG D C 48Vdc Max 20mA Max Table 1 Electrical Ratings 2 Warnings WARNINGS USE COVER BOLTS CLASS A4 70 DO NOT OPEN WHEN AN...

Страница 2: ...I Zone 1 AEx db IIC T6 Gb Ta 55 C to 60 C Zone 21 AEx tb IIIC T75 C Db Ta 55 C to 60 C GNExCP7 BG D GNExCP7 BG D L GNExCP7 BG D C Class I Zone 1 AEx db IIC T6 Gb Ta 55 C to 60 C Zone 21 AEx tb IIIC T...

Страница 3: ...G D C ATEX IECEx UKEx 75 C GNExCP7 BG S GNExCP7 BG S L GNExCP7 BG S C Class Zone 90 C GNExCP7 BG D GNExCP7 BG D L GNExCP7 BG D C Class Zone Ambient Temperature Range 55 C to 70 C 67 F to 158 F ATEX IE...

Страница 4: ...Never use the cover bolts to force the cover into position 9 Earthing The units are provided with internal and external earth terminals which are mounted in the base of the unit Internal earthing con...

Страница 5: ...erature C 35 40 45 50 55 60 req Cable Cable Gland rating C 61 66 71 76 81 86 For Dual Switch model GNExCP7 BG D Max ambient temperature C 20 25 30 35 40 45 50 55 60 req Cable Cable Gland rating C 65 7...

Страница 6: ...nnected to each terminal way In most configuration an input and output wire can be fitted to individual terminals where these are more complex and if fitting 2 off wires to one terminal way the sum of...

Страница 7: ...tage and type of components fitted If a combination of resistors diodes zener diodes is used values for all components must be observed and lowest current limit for either component becomes overall li...

Страница 8: ...pheres Electrical IEC 60079 17 installations inspections and maintenance Electrostatic charging hazard clean only with a damp cloth Units must not be opened while an explosive atmosphere is present Fo...

Страница 9: ...ations 2 3 5 6 7 8 LED Indicator Wiring Configurations 4 5 6 8 Parallel Dual Switch Wiring Configurations 7 8 S D 1 N SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u SERIES MODULE s Single...

Страница 10: ...xZ LED N A L or C Dual DIN Rail Default NO LED D D 1 N Dual DIN Rail Only Default NO LED Series Device D D 1 N Sxxxx Dual DIN Rail Only Default NO LED EOL Series D D 1 N Exxxx Sxxxx Dual DIN Rail Only...

Страница 11: ...Rail Only Duplicated NO LED Series Device D D 2 N Sxxxx Dual DIN Rail Only Duplicated NO LED EOL Series D D 2 N Exxxx Sxxxx Dual DIN Rail Only Alt EOL Pos n DUP NO LED EOL Series D D Y N Exxxx Sxxxx...

Страница 12: ...ingle DIN Rail Default LED with RL1 EOL Device S D 1 L Exxxx Single DIN Rail Default LED with RL1 EOL Series Device S D 1 L Exxxx Sxxxx SHEET 4 S D W L Exxxx Sxxxx Single DIN Rail Alt EOL Pos n LED wi...

Страница 13: ...D D 1 L Sxxxx Dual DIN Rail Only Default LED with RL1 Series Device Dual DIN Rail Only Alt EOL Pos n LED with RL1 EOL Series D D W L Exxxx Sxxxx SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATO...

Страница 14: ...D D 2 L Sxxxx Dual DIN Rail Only Duplicated EOL SERIES LED with RL1 Series Device Dual DIN Rail Only Alt EOL Pos n DUPLICATED LED with RL1 EOL Series D D Y L Exxxx Sxxxx SWITCH TYPE s TERMINALS t PRO...

Страница 15: ...E s TERMINALS t PRODUCT OPTION o LED INDICATOR u SERIES MODULE s D D P N Sxxxx Dual DIN Rail Parallel Wiring No LED Series Device SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u MODULE e s...

Страница 16: ...Dual DIN Rail Parallel Wiring LED with RL1 EOL Device SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u MODULE e s D D V L Exxxx Sxxxx Dual DIN Rail Only Parallel Wiring Alt EOL LED with RL1...

Страница 17: ...as shown in terminal Default Link wire replaced by Series device in terminal SERIES 1 EOL 1 M S 1 EOL 1 1 2 3 3 2 1 6 5 4 3 2 1 M S 1 Circuit as shown in Unoperated condition Unoperated Condition Glas...

Страница 18: ...Series Dual PCB Version Default NO LED D P 1 N DUAL SWITCH WITH EOL SERIES DEVICES CONFIG P2 1 SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u DUAL SWITCH EOL 2 M S 1 M S 2 3 2 1 M S 2 1 2...

Страница 19: ...WITH EOL ALT SERIES DEVICES DUPLICATED SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u MODULES e s CONFIG P3 2 CONFIG P3 1 SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u MODULES...

Страница 20: ...ngle PCB Version Default LED with RL1 EOL Series S P W L Exxxx Sxxxx Single PCB Version Alt EOL Pos n LED with RL1 EOL Series SHEET 4 S P 1 L SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u...

Страница 21: ...1 L DUAL SWITCH WITH LED EOL SERIES DEVICES CONFIG P5 1 SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u DUAL SWITCH WITH LED EOL 2 M S 1 M S 2 3 2 1 M S 2 1 2 3 4 5 6 SERIES 2 1 2 3 Default...

Страница 22: ...e s CONFIG P6 2 SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u MODULES e s D P 2 L Exxxx Sxxxx Dual PCB Version Duplicate EOL Series LED with RL1 EOL Series DUAL SWITCH WITH LED EOL SERIES...

Страница 23: ...LED D P P N DUAL SWITCH PARALLEL WITH EOL SERIES DEVICES CONFIG P7 1 SWITCH TYPE s TERMINALS t PRODUCT OPTION o LED INDICATOR u DUAL SWITCH PARALLEL M S 1 M S 2 1 2 3 4 5 6 Circuit as shown in Unoper...

Страница 24: ...x Dual PCB Version Parallel Wiring LED with RL1 EOL Series Dual PCB Version Parallel Wiring LED with RL1 D P P L DUAL SWITCH PARALLEL WITH LED EOL SERIES DEVICES CONFIG P8 1 SWITCH TYPE s TERMINALS t...

Страница 25: ...o EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality A...

Страница 26: ...Place of Issue London 14 09 2023 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market...

Страница 27: ...UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex d IIC T6 T4 Gb II 2D Ex tb IIIC T100 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1...

Отзывы: