![E2S GNExCP7-BG-S Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/e2s/gnexcp7-bg-s/gnexcp7-bg-s_instruction-manual_3457185002.webp)
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880
Document No. D204-00-011-IS
Issue 3 25-08-2023 Sheet 2 of 8
3) Marking & Rating Information
The GNExCP7-BG Call Points comply with the following standards
for hazardous locations:
3.1
Class/Division Ratings for US & Canada
All models are approved for use as Alarm System use:
UL 60947-4-1 LOW-VOLTAGE SWITCHGEAR AND
CONTROLGEAR - PART 4-1: CONTACTORS AND
MOTORSTARTERS - ELECTROMECHANICAL
CONTACTORS AND MOTOR-STARTERS- Edition 3 -
Revision Date 2017/10/17
CSA C22.2 NO. 60947-4-1-14 LOW-VOLTAGE
SWITCHGEAR AND CONTROLGEAR — PART 4-1:
CONTACTORS AND MOTOR-STARTERS —
ELECTROMECHANICAL CONTACTORS AND MOTOR-
STARTERS- Edition 2 - Issue Date 2014/01/04
For Indoor and Outdoor Use
Pour usage Interier INTÉRIEUR
Ambient Temperature Range:
-55°C to +60°C
Standards
UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: Equipment -
General requirements
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: Equipment
protection by flameproof enclosures “d”
UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31: Equipment
dust ignition protection by enclosure "t"
CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres – Part 0:
Equipment – General requirements
CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive Atmospheres – Part 1:
Equipment protection by flameproof enclosures “d”
CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive Atmospheres – Part 31:
Equipment dust ignition protection by enclosure “t”
Class Division Ratings for US (NEC) & Canada (CEC)
Model No:
Rating
GNExCP7-BG-S
GNExCP7-BG-S-L
GNExCP7-BG-S-C
GNExCP7-BG-D
GNExCP7-BG-D-L
GNExCP7-BG-D-C
Class I Div 2 Group ABCD T6 Ta -55°C to
+60°C
Class II Div 2 Group FG T5 Ta -55°C to
+60°C
Class III Div 2 Ta -55°C to +60°C
Class Zone Ratings for US (NEC)
Model No:
Rating
GNExCP7-BG-S
GNExCP7-BG-S-L
GNExCP7-BG-S-C
Class I Zone 1 AEx db IIC T6 Gb Ta -55°C
to +60°C
Zone 21 AEx tb IIIC T75°C Db Ta -55°C to
+60°C
GNExCP7-BG-D
GNExCP7-BG-D-L
GNExCP7-BG-D-C
Class I Zone 1 AEx db IIC T6 Gb Ta -55°C
to +60°C
Zone 21 AEx tb IIIC T90°C Db Ta -55°C to
+60°C
Class Zone Ratings for Canada (CEC)
Model No:
Rating
GNExCP7-BG-S
GNExCP7-BG-S-L
GNExCP7-BG-S-C
Ex db IIC T6 Gb Ta -55°C to +60°C
Ex tb IIIC T75°C Db Ta -55°C to +60°C
GNExCP7-BG-D
GNExCP7-BG-D-L
GNExCP7-BG-D-C
Ex db IIC T6 Gb X Ta -55°C to +60°C
Ex tb IIIC T90°C Db Ta -55°C to +60°C
Installation must be carried out in compliance with the National Electric
Code / Canadian Electric Code
3.2
ATEX / IECEx & UKEx Ratings
Standards
EN60079-0:2018/IEC60079-0:2017 (ed.7): Explosive Atmospheres -
Equipment General Requirements.
EN60079-1:2014/IEC60079-1:2014 (ed.7): Explosive Atmospheres -
Equipment Protection by Flameproof Enclosures “d”.
EN60079-31:2014/IEC60079-31:2022 (ed.3): Explosive Atmospheres -
Equipment Dust Ignition Protection by enclosure “t”.
Model No:
Rating
GNExCP7-BG-S
Ex db IIC T6 Gb Ta –55°C to +70°C
Ex tb IIIC T80°C Db Ta –55°C to +70°C
GNExCP7-BG-D
GNExCP7-BG-S-L
GNExCP7-BG-S-C
Ex db IIC T5 Gb Ta –55°C to +70°C
Ex db IIC T6 Gb Ta –55°C to +65°C
Ex tb IIIC T85°C Db Ta –55°C to +70°C
GNExCP7-BG-D-L
GNExCP7-BG-D-C
Ex db IIC T4 Gb Ta –55°C to +70°C
Ex db IIC T5 Gb Ta –55°C to +65°C
Ex db IIC T6 Gb Ta –55°C to +50°C
Ex tb IIIC T100°C Db Ta –55°C to +70°C
See Product table for electrical ratings of each unit model
Certificate No.
DEMKO 19 ATEX 2101X
IECEx ULD 19.0007X
UKEx UL UL21UKEX2134X
Epsilon x
Equipment Group
and Category:
II 2G
II 2D
CE Marking and
Notified Body No.
2813
UKCA Marking and
Notified Body No.
0518
3.3
DNV Type Approval
The units have been tested and approved for the installation
on ships in the following locations:
Temperature
: Class A,B,C & D (all locations including
open decks and masts)
Humidity:
Class A & B (all locations)
Vibration:
Class A (all locations except installation on
machinery such as combustion engines,
compressors, pumps, including piping on
such machinery)
EMC:
Class A & B (all locations including open
decks and bridge)
Enclosure:
Class A, B & C – IP56 (all locations except
submerged applications and bilges)