E2S GNExCP7-BG-I Скачать руководство пользователя страница 8

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           www.e2s.com              Tel: +44 (0)208 743 8880 

Document No. D202-00-501-IS 

Issue 1        28-01-2024                         Sheet 8 of 9                                                                                            

 

Integrity in respect of failure to close 

SIL 2 

System Type 

Hardware Fault Tolerance 

Safe Failure Fraction (credible claim) 

75% 

PFD (hazardous failure) 

2.3 x 10

-3

 

Proof Test Interval 

Up to 1 year 

 

 
 

17) 

Electrical System Design For Installation In 
Hazardous Areas Using Zener Barriers

 

 
 

ATEx/IECEx & UKEx Installations: 

 

17.1  Single Input Barrier 

Where the call point switch uses a Zener barrier, as shown in 

Fig below. 

 

 

 

Fig. Single stage call point alarm using single barrier. 

 

 

NEC /CEC Installations: 

 

17.2  Single Input Barrier 

Where the call point switch uses a Zener barrier, as shown in 

Fig below. 

 

 

 

 

Fig. Single stage call point alarm using single barrier. 

 

 

 

 

 

 

1.  Associated apparatus output current must be limited 

by a resistor such that the output voltage current 
plot is a straight line drawn between open-circuit 
voltage and short-circuit current. 

 

2.  Installed should be in accordance with its 

manufacturer’s control drawing and Article 504 of 
the National Electrical Code (ANSI/NFPA 70) for 
Canadian installation in the United States, or 
Section 18 of the Electrical Code for installations in 
Canada. 

 

3.  Where the cable capacitance and inductance per 

foot are not known, the following values shall be 

used: Ccable = 60 pF/ft., Lcable = 0.2 

μ

H/ft. 

 

4.  When required by the manufacturer’s control 

drawing, the associated apparatus must be 
connected to a suitable ground electrode per the 
National Electrical Code (ANSI/NFPA 70), the 
Canadian Electrical Code, or other local installation 
codes, as applicable. The resistance of the ground 
path must be less than 1 ohm. 
 

 
 

18) 

Electrical System Design For Installation In 
Hazardous Areas Using Galvanic Isolators

 

 

Galvanic isolators do not require a high integrity earth 

connection. For small systems where a high integrity earth is 

not already available, the use of galvanic isolators often 

reduces the overall installation cost and simplifies design. 

 

ATEx/IECEx & UKEx Installations: 

 

13.1  Single Input Barrier 

Where the call point switch uses a single Zener barrier, as 

shown in Fig below. 

 

 

 

Fig. Single stage call point alarm using single galvanic 

isolator. 
 
 
 
 
 
 
 
 
 
 
 

Содержание GNExCP7-BG-I

Страница 1: ...8 743 8880 Document No D202 00 501 IS Issue 1 28 01 2024 Sheet 1 of 9 GNExCP7 BG I GNExCP7 BG IR 1 Product Table Unit Type Code Input Parameters GNExCP7 BG I GNExCP7 BG IR Ui 30V Ii 500mA Pi 1100mW Ci...

Страница 2: ...atings Standards EN60079 0 2018 IEC60079 0 2017 ed 7 Explosive Atmospheres Equipment General Requirements EN60079 11 2012 IEC60079 11 2019 ed 6 Explosive Atmospheres Equipment Protection by Intrinsica...

Страница 3: ...uit and parts which may be earthed This shall be considered in the end use application to ensure the possibility of an earth connection will not compromise intrinsic safety Use galvanically isolating...

Страница 4: ...x certified Zener barrier or galvanic isolator which have output parameters equal to or less than 30V 500mA and 1100mW where Io is resistively limited The cable parameters stated on the selected Zener...

Страница 5: ...n and allows for the wiring of switches only Model GNExCP7 BG I For full wiring details see wiring diagrams D202 06 501 The PCB Terminal Version has a 6 way connector but is designed to allow for full...

Страница 6: ...iclockwise 90 to its original vertical position The glass element should now raise up so it is level again horizontal in the viewable window Replace the cover plate and tighten the 4 off M4 cap head s...

Страница 7: ...tions inspections and maintenance For US CEC Class Div Zone UL 60079 19 Explosive atmospheres Equipment repair overhaul and reclamation UL 60079 17 Explosive atmospheres Electrical installations inspe...

Страница 8: ...ween open circuit voltage and short circuit current 2 Installed should be in accordance with its manufacturer s control drawing and Article 504 of the National Electrical Code ANSI NFPA 70 for Canadia...

Страница 9: ...le stage call point alarm using single galvanic isolator 1 Associated apparatus output current must be limited by a resistor such that the output voltage current plot is a straight line drawn between...

Страница 10: ...IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY SYSTEMS LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 Introd...

Страница 11: ...R N Exxxx Sxxxx Single PCB Version With EOL Series NO LED EOL Series S P W N Exxxx Sxxxx Single PCB Version Alt EOL Pos n NO LED EOL Series SHEET 1 PRODUCTS GNExCP7 STExCP8 WP7 S P R N SWITCH TYPE s...

Страница 12: ...rance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 1G Ex ia IIC T6 T4 Ga Standards applied EN 60079 0 2018 EN 60079 11 2012 Directive 2014 30 EU Electromagnetic Com...

Страница 13: ...ion Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 1G Ex ia IIC T6 T4 Ga Standards applied EN 60079 0 2018 EN 60079 11 2012 Directive 2014 30 EU Electromagnetic Compatibility Direc...

Отзывы: